Switching capacity
acc. to IEC/EN 60947-1; IEC/EN 60947-3; IEC/EN 60947-5-1:
Control switch 8008/2-0, 8008/2-1
Load disconnect switch 8008/2-6
Short-circuit
protection
Back-up fuse max. 32 A gG
Note: The overload protection of the consumers must be performed
independently of the back-up fuse.
Rated short-time
withstand current Icw
0,3 kA (1s)
Service life
mechanical: 500,000 operating cycles
Ambient conditions
Operating
temperature
-60 ... +80 °C
Technical Data
AC-1
AC-11
AC-15
DC-13
(L/R=300 ms)
690 V, 16 A
660 V, 2.5 A
415 V, 16 A
230 V, 0.4 A
500 V, 4 A
380 V, 6 A
220 V, 6 A
DC-11
(L/R=100 ms)
DC-11
(L/R=50 ms)
DC-11
(L/R=1 ms)
220 V, 0.4 A
220 V, 0.6 A
220 V, 1.0 A
110 V, 1.0 A
110 V, 1.6 A
110 V, 4.0 A
60 V, 4.0 A
60 V, 6.0 A
60 V, 16.0 A
AC-3
DC-1
DC-3
DC-5
690 V, 16 A
60 V, 10 A
1)
60 V, 4 A
1)
60 V, 2.5 A
1)
60 V, 10 A
2)
60 V, 10 A
2)
60 V, 6 A
2)
110 V, 10 A
2)
110 V, 6 A
2)
110 V, 4 A
2)
60 V, 10 A
3)
60 V, 10 A
3)
60 V, 10 A
3)
110 V, 10 A
3)
110 V, 10 A
3)
110 V, 6 A
3)
220 V, 10 A
3)
220 V, 4 A
3)
220 V, 2 A
3)
1)
1 conducting path
2)
2 conducting paths in series
3)
3 conducting paths in serie