Installation 

 

  WARNING 

To avoid fire or shock hazard, the electrical power must be 

turned OFF before and during installation. 

      Refer to the technical data and installation information on 

the  front  and  side  mounted  nameplates  of  the  control 
unit. 

 

   For Class I, Zone 1 installations, Series 8008/2 control 

and load switch must be installed in a Certified Increased 
Safety 'eb' enclosure.  When installing the control 
components into 'eb' enclosures the spacing distances 
through air and over surface, in accordance with 
CAN/CSA C22.2 No. 60079-7 + C22.2 No. 14 for 
Canada or ANSI/ISA 60079-7 + UL508A for USA, must 
be maintained.   

••••

 

For Class I, Division 2 installations Series 8008/2 control and 
load switch must be installed in a suitable enclosure providing 
mechanical protection, provisions for conduit/cable entry, and 
sufficient clearance for electrical connections as per C22.2 No. 
14 for Canada and UL508A for USA. 

••••

 

Series 8008/2 control and load switch have been Certified as 
a component and the suitability of the final assembly is to be 
determined by the authorities having jurisdiction.  

••••

 

The terminals on the control component have been identified on the 
control unit.  Refer to the device label and technical information for 
proper connection. 

••••

 

Field wiring conductors shall be copper wires only, stranded – 
and sized based on the conductor rated for 75°C.(for North 
American Installations) 

••••

 

Per NEC 505.7(E), the short circuit current needs to be limited to 
less than 10,000 rms symmetrical amperes. 

 

Maintenance 

 

  WARNING 

To avoid electrical shock, fire and/or explosions, always 
disconnect primary power source before inspection, 
service or Maintenance. 

 

We recommend an Electrical Prevention Maintenance program 
as described in the National Electrical Code

®

 (NEC) and the 

National Fire Protection Association Bulletin NFPA No. 70B 
or the Canadian Electrical Code (CEC) respectively, and any 
local regulations. It is recommended that it should be at least once 
a year. 

••••

 

Maintenance should only be performed by qualified and 
experienced personnel. 

••••

 

Perform visual, electrical, and mechanical checks on all 
components on a regular basis. 

••••

 

Visually check for undue heating evidence by 
distortion of wires or other components, 
damaged or worn parts. 

••••

 

Electrically  check  to make  sure  that all  connections  are 
clean and tight. 

••••

 

Mechanically check that all parts are properly assembled, 
and operating mechanisms move freely. 

••••

 

The Flameproof joint CANNOT be repaired

 

••••

 

Replacement parts are available through R. STAHL 

distributors.  Replace only with parts of identical rating

.   

 

 

Содержание 8008/2

Страница 1: ...ompetent personnel Read entire instructions before starting installation of this product Contact your R STAHL Customer Service or R STAHL distributor if you have any questions Technical information and illustrations are not binding and subject to change without notice The nature of these instructions is only informative and does not cover all of the details variations or combinations in which this...

Страница 2: ...Standard for Safety for Electrical Apparatus for Explosive Gas Atmospheres Part 1 Flameproof enclosures d ANSI ISA 60079 7 Electrical Apparatus for Explosive Gas Atmospheres Part 7 Increased Safety e ANSI UL 508 Standard for Industrial Control Equipment 5 Safety Instructions Use the control and load switch only for its intended purpose Incorrect or impermissible use or non compliance with these in...

Страница 3: ... Rating A600 per ANSI UL 508 and CSA C22 2 No 14 Maximum current resistive 10 A 8008 2 6 Load Switch Voltage Rating Phase Horsepower rating 120 VAC 3 phase 2 hp 240 VAC 3 phase 5 hp 480 VAC 3 phase 10 hp 600 VAC 3 phase 10 hp Maximum current resistive 16 A Note Per NEC 505 7 E the short circuit current needs to be limited to less than 10 000 rms symmetrical amperes Termination Capacity Contact ter...

Страница 4: ...iedonthe control unit Refertothedevicelabel and technical informationfor properconnection Field wiring conductors shall be copper wires only stranded and sized based on the conductor rated for 75 C for North American Installations Per NEC 505 7 E the short circuit current needs to be limited to less than 10 000 rms symmetrical amperes 8 Maintenance WARNING To avoid electrical shock fire and or exp...

Страница 5: ...80 086 09 30 0 251341 5 5 S I0M 8008 01 en 2016 07 18 9 Dimensions in Millimeters ...

Отзывы: