Explosion Protected 

Control and Load Switch  

(8008/2)  

 

 

 

 

Contents 

1. Contents  ................................................................. 1 
2. General Information  ....................................................... 1 
3. Application  .............................................................. 1 
4. Hazardous Location Ratings and Applicable 

Standards  ……………………………………………..2 

5. Safety Instructions  …………………………………….2 
6. Technical Data  …………………………………………3 
7. Installation  …………………………………………………4 
8. Maintenance  …………………………………………..4 
9. Dimensions in Millimeters  ……………………………...5 

General Information 

2.1   Contact Information 

R. STAHL Inc. 
13259 N. Promenade Blvd. 
Stafford, TX 77477 

Phone: 

+1 832 539 6700 

Fax: 

+1 281 313 9302 

Internet:   

www.rstahl.com  

R. STAHL Schaltgeräte GmbH 
Am Bahnhof 30 
D-74638 Waldenburg 
Phone: 

+49 7942 943-0 

Fax: 

+49 7942 943-4333 

Internet: 

www.stahl.de 

2.2  

Information regarding this Installation, Operation and 
Maintenance Sheet 

ID NO.: 

251341 / 80 086 09 30 0 

Publication Code:  S-I0M-8008-00-en-2016-07-27  

The explosion protected control components 
should be installed, inspected, maintained, 
and operated by qualified and competent 
personnel. Read entire instructions 
before starting installation of this product. 

Contact your R. STAHL Customer Service or  
R. STAHL distributor if you have any questions. 

Technical information and illustrations are not 
binding and subject to change without notice. 

The nature of these instructions is only informative 
and does not cover all of the details, variations or 
combinations in which this device may be used, its 
storage, delivery, installations, safe operation and 
maintenance. 

Since conditions of use of the product are outside of 
the care, custody and control of the manufacturer, the 
purchaser should determine the suitability of the 
product for his intended use, and assumes all risk and 
liability whatsoever in connection therewith. 

Save these instructions for future reference. 

Application 

The series 8008 – Control and load switch (industrial control 
equipment) – is a flameproof switch with increased safety 
terminals suitable to make or break power supplies in 
hazardous (classified) locations. The switch is a modular design 
of up to 4 poles. 

Refer to section 6 for application and details of  the control 
devices. 

 

Содержание 8008/2

Страница 1: ...ompetent personnel Read entire instructions before starting installation of this product Contact your R STAHL Customer Service or R STAHL distributor if you have any questions Technical information and illustrations are not binding and subject to change without notice The nature of these instructions is only informative and does not cover all of the details variations or combinations in which this...

Страница 2: ...Standard for Safety for Electrical Apparatus for Explosive Gas Atmospheres Part 1 Flameproof enclosures d ANSI ISA 60079 7 Electrical Apparatus for Explosive Gas Atmospheres Part 7 Increased Safety e ANSI UL 508 Standard for Industrial Control Equipment 5 Safety Instructions Use the control and load switch only for its intended purpose Incorrect or impermissible use or non compliance with these in...

Страница 3: ... Rating A600 per ANSI UL 508 and CSA C22 2 No 14 Maximum current resistive 10 A 8008 2 6 Load Switch Voltage Rating Phase Horsepower rating 120 VAC 3 phase 2 hp 240 VAC 3 phase 5 hp 480 VAC 3 phase 10 hp 600 VAC 3 phase 10 hp Maximum current resistive 16 A Note Per NEC 505 7 E the short circuit current needs to be limited to less than 10 000 rms symmetrical amperes Termination Capacity Contact ter...

Страница 4: ...iedonthe control unit Refertothedevicelabel and technical informationfor properconnection Field wiring conductors shall be copper wires only stranded and sized based on the conductor rated for 75 C for North American Installations Per NEC 505 7 E the short circuit current needs to be limited to less than 10 000 rms symmetrical amperes 8 Maintenance WARNING To avoid electrical shock fire and or exp...

Страница 5: ...80 086 09 30 0 251341 5 5 S I0M 8008 01 en 2016 07 18 9 Dimensions in Millimeters ...