Compact Sheet-steel
Emergency Light Fitting
Series 6118/1
8.3.2 Electrical connections
Electrical connection
Observe the maximum clamping possibility of the connecting terminals (see chapter
"Technical data").
For optional screw terminals, two conductors per clamping unit can be clamped (ingoing
and outgoing wiring).
Observe the following when connecting to the main supply:
• Clamping must be carried out precisely!
• Do not clamp any part of the conductor insulation!
• Do not interchange the conductors!
• Observe the technical regulations when connecting the conductor!
• Clamp the conductor firmly.
• Do not remove the terminal cover of optional screw terminals to clamp the conductor!
• The phase L1 must be directly connected to the grid which functions as charging
phase for the battery!
Installing cable in the luminaire
• Optional screw-type terminals: Firmly tighten screws (tightening torque 2 Nm, for un
-
used clamping units 0.7 Nm)!
NOTICE
Danger due to wrong connection.
Malfunction
• Phases L and L1 must be connected in phase.
18457E00
• Install the cable in the luminaire as
marked (see figure on the left).
• Use factory mounted cable holders.