10.1 Maintenance
• Consult the relevant national regulations to determine the type and extent of
inspections.
• Adapt inspection intervals to the operating conditions.
At a minimum, check the following points during maintenance work on the device:
• If the cables have been clamped properly
• If the enclosure, seals and surface of the plug pins are damaged
• If the contact pins are dirty; if necessary, clean them
• Whether the permissible temperatures are complied with
• Intended use
10.2 Overhaul
10.3 Repair
Observe the relevant national regulations in the country of use.
• To avoid corrosion, the plug must be disconnected regularly.
• If required, clean the plug pins.
• After 1000 mating cycles, it is advisable to apply contact oil
(e.g. KLÜBERALFA KRA 3-730) to the device.
The use of mineral-oil-based lubricants is impermissible!
DANGER
Explosion hazard due to improper repair!
Non-compliance results in severe or fatal injuries.
• Repair work on the devices must be performed only by
R. STAHL Schaltgeräte GmbH.