Roughly align the laser using the built-in vial, i.e. set the bubble roughly in the

centre of the vial. Turn the deflector prism's beam emission opening by hand in
the direction of the wall. 

The LAPR-150 rotation laser has been designed for building site use and leaves our
factory perfectly calibrated. As with any precision instrument, however, its 
calibration must be regularly checked. The unit should be checked before starting
any new tasks, particularly when the unit has been exposed to strong vibrations.
After an impact, the unit should be checked throughout its whole self-leveling
range. 

Checking the calibration

H

Horizontal check

1.

2.

3.

7.

4.

5.

6.

If the difference between the control points is less than 2mm ( 1/8”) at 5m ( 26ft )
distance and 4mm ( 3/16” ) at 10m ( 39ft ) distance the permissible tolerance of 
± 0.2 mm/m  ( ± 1/4”  over 100ft ) is being maintained.

Repeat steps 4 and 5 to obtain Points 3 and 4. 

Mark the position of the visible laser dot on the wall (Point 2).

Mark the position of the visible laser dot on the wall - Measurement 1 (Point 1).
Because the diameter of the beam depends on the distance, you must always
only use the center of the dot! 

Set up the rotation laser on a smooth, level surface or on a tripod 5m ( 26 ft )
or 10m ( 39ft ) from a wall with the front side facing the wall.

Turn the complete unit 90° without altering the height of the laser (i.e. the tripod
must not be altered) and turn the deflection prism in the direction of the wall
again in the area of measurement point 1. 

C

H1

H2

H3

H4

Содержание LAPR-150

Страница 1: ......

Страница 2: ...O 3a 3b 10 ...

Страница 3: ...A 2 7 6 12 11 1 8 4b 4a 5b 5c 9 5a 13 ...

Страница 4: ...F C B E D G ...

Страница 5: ...I K L M s 17ft H 26ft 39ft max 1 8 3 16 ...

Страница 6: ...beam can be received at distances of up to 90 m 570 ft with the use of a receiver even when it is no longer visible to the naked eye O 3b 4a 4b Main components SP1 vertical beam emission aperture SP2 rotation beam emission aperture ON switch Selector switch Rotation function Selector switch Scan function LEDs for displaying LED red battery voltage and overheat Shock protection 5 8 threaded connect...

Страница 7: ...laser dot is marked Getting started Move the slider switch 3a upwards to switch the laser ON If the unit is outside its self leveling range the laser starts to flash Aligning 1 2 3 Re fasten the clamp Tilt the upper part of the casing until the bubble in the vial no longer touches the edge of the vial Release the clamp Adjusting and aligning the laser beam 1 2 The LAPR 150 can be used in 2 operati...

Страница 8: ...sing by turning the unit on the base plate Because of the vibration that this may cause the monitoring function may cause the laser beam to flash Generating parallel planes Creating vertical reference areas e g measuring dividing walls Measuring tiles panels parquet floors ceilings walls measuring right angles simply by swiveling the unit At right angles to the wall 2 basic methods of vertical lev...

Страница 9: ... 4 5 6 If the difference between the control points is less than 2mm 1 8 at 5m 26ft distance and 4mm 3 16 at 10m 39ft distance the permissible tolerance of 0 2 mm m 1 4 over 100ft is being maintained Repeat steps 4 and 5 to obtain Points 3 and 4 Mark the position of the visible laser dot on the wall Point 2 Mark the position of the visible laser dot on the wall Measurement 1 Point 1 Because the di...

Страница 10: ...e unit 180 without altering the height of the laser The tripod must not be altered Mark the center of the laser dot on wall A for Point 4 Measure the corresponding heights of the points either in relation to the floor or to the point below which is classed as being at 0 mm It is essential that the plus or minus signs are calculated correctly 15 Switch the unit on 16 17 18 Direct the laser beam on ...

Страница 11: ...Only use 1 5V mono cells size D Replacing the batteries Suitable rechargeable batteries can also be used 1 2 Tip Remove the batteries if the unit will not be used for a long period Operating status display and error messages via the LEDs Illuminated green LED laser outside the self leveling range laser in operation battery voltage very low battery replacement required imminently battery voltage ve...

Страница 12: ... from accidental short term exposure to the laser beam by the lid closing reflex and or the reflex reac tion to turn one s head This equipment can therefore be used without additio nal protective measures Nevertheless you should not look directly into the laser beam The laser goggles enclosed with these units are not safety goggles They are designed to make the laser light easier to see Do not let...

Страница 13: ...cision optical instrument Stabila provides a guarantee against deficiencies and faults in the assured characte ristics because of material or manufacturing faults for a period of 24 months from date of purchase Any faults will be eliminated at Stabila s own discretion either by repairing or replacing the unit Stabila accepts no wider claims No liability is accepted for any faults due to inappropri...

Отзывы: