8
ELECTRICAL
To avoid dangerous or fatal electrical shock, turn OFF power to motor
before working on electrical connections.
Plug the System into a Ground Fault Circuit Interrupter (GFCI) pro-
tected receptacle on a 115 Volt, 60 Hertz grounded circuit only.
GFCI tripping indicates an electrical problem. If GFCI trips and will not
reset, have a qualified electrician inspect and repair electrical
system.
Exactly match supply voltage to nameplate voltage (115 Volt single
phase). Incorrect voltage can cause fire or damage motor and voids
warranty!
Voltage:
Voltage at motor must not be more than 10% above or below motor name-
plate rated voltage (115 Volts) or motor may overheat, causing overload trip-
ping and reduced component life. If voltage is less than 104 Volts or more
than 126 Volts when motor is running at full load, consult power company.
Grounding:
Pump is supplied with grounded 3-wire cord and plug. Do not modify cord or
plug. Plug into GFCI protected, grounded outlet only.
Wiring:
Protect cord from water and from physical damage to avoid serious or
fatal electrical shock hazard.
Plug the System into a GFCI receptacle on a 115 Volt, 60 Hertz grounded cir-
cuit only. Electrically isolate circuit so that no other lights or appliances use it.
Consult a licensed electrician if such a circuit is not available.
Do not modify cord, plug or receptacle! If an existing circuit must be used
and the receptacle and factory installed plug do not match exactly, consult a
licensed electrician.
Do not use an extension or drop cord with the System: It could cause a fire
hazard or low voltage problems; wet cords pose shock hazards. Extension
cords can easily become cut or frayed and dangerous when placed across
yard areas or walkways.
Match circuit breaker to Table III, below.
Values given in table are for PUMP MOTOR ONLY. If additional
accessories are installed on pump motor circuit (heater, lights, etc.,)
include their amperage draw when figuring wire and circuit breaker
sizes.
TABLE III - RECOMMENDED FUSING DATA - 60 HZ 115V MOTORS
System Suffix
Motor
Full Load
Branch Circuit Breaker
No.
H.P.
(amps)
Rating (amps)
-03, -04
3/4
9.0
15
-03, -04, -11
1
12.0
15
Hazardous voltage.
Can shock, burn,
or cause death.
Connect pump
to GFCI protected,
grounded power
supply.