Voltage:
Voltage at motor must be not more than 10% above or below motor name-
plate rated voltage or motor may overheat, causing overload tripping and re-
duced component life. If voltage is less than 90% or more than 110% of rated
voltage when motor is running at full load, consult power company.
Values given in tables below are for PUMP MOTOR ONLY. If addi-
tional spa accessories are installed on pump motor circuit (heater,
blower, etc.), include their amperage draw when figuring wire and circuit
breaker sizes.
L2
B
A
L1
Lo
Hi
Timer Motor
Supply
Lo
Hi
Circuit
Protector
Remote
SPDT
Switch
Ground
(Green)
Common
Remote Switching For 2-Speed Pumps
Timer (optional)
Low Speed Only
Minimum switch and timer amp rating must equal Branch Fuse Rating
given in "Recommended Circuit Breaker Size and Wiring Data" table.
TABLE I - RECOMMENDED CIRCUIT BREAKER SIZE AND WIRING DATA FOR 60 Hz MOTORS
Branch
AWG (mm
2
) Wire Gauge Size
Full
Circuit
Dist in Ft. (M) - Service to Motor
Model
Motor
Load
Breaker
0-100
101-200
201-300
Temp
No.
HP
Volts
Amps
Amp Rating
(0-30)
(31-60)
(61-90)
Deg. C.
Single Speed Pumps:
JSACLC-A
1/2
115
8.0
15
14 (2.0)
12 (3.0)
10 (5.5)
75
JSADLC-A
3/4
115
11.25
15
14 (2.0)
10 (5.5)
8 (8.4)
75
JSAELC-A
1
115
14.0
20
12 (3.0)
10 (5.5)
8 (8.4)
75
JSAFLC-A
1-1/2
115/230
16.4/8.2
25/15
12/14 (3.0/2.0)
8/14 (8.4/2.0)
6/12 (14.0/3.0)
75
JSAEFLC-A
1-1/2
115/230
14.4/7.2
20/15
12/14(3.0/2.0)
10/14 (5.5/2.0)
8/14 (8.4/2.0)
75
Two Speed Pumps:
JSAYDLC-A
3/4-1/8
115
9.6
15
14 (2.0)
10 (5.5)
8 (8.4)
75
JSAYDLC-LA
3/4-1/8
115
9.0
15
14 (2.0)
12 (3.0)
10 (5.5)
75
JSAYELC-A
1-1/6
115
12.5
20
12 (3.0)
10 (5.5)
8 (8.4)
75
JSAYELC-LA
1-1/6
115
12.0
15
12 (3.0)
10 (5.5)
8 (8.4)
75
JSAYFLC-LA
1
1
⁄
2
- 1/6
115
16.6
25
10 (5.5)
8 (8.4)
6 (14.0)
75
JSAYFLC-230A
1
1
⁄
2
- 1/6
230
8.1
15
14 (2.0)
14 (2.0)
12 (3.0)
75
JYSE-100
1-1/6
115
11.6
15
14 (2.0)
10 (5.5)
8 (8.4)
75
JSYF-150
1
1
⁄
2
- 1/6
230
9.4
15
14 (2.0)
14 (2.0)
12 (3.0)
75