9.1.11 T_FAST
The T_FAST register contains the maximum fast decay time (TOFF_FAST) and the
maximum fall step time (FALL_STEP) used by the current control system (see
for details):
The available range for both parameters is from 2 µs to 32 µs.
Any attempt to write to the register when the motor is running causes the command to be
ignored and NOTPERF_CMD to rise (see
9.1.12 TON_MIN
The TON_MIN register contains the minimum ON time value used by the current control
system (see
The available range for both parameters is from 0.5 µs to 64 µs.
Any attempt to write to the register when the motor is running causes the command to be
ignored and the NOTPERF_CMD to rise (see
Table 13. T_FAST register
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
TOFF_FAST
FAST_STEP
Table 14. Maximum fast decay times
TOFF_FAST [3 … 0] FAST_STEP [3 … 0]
Fast decay time
0 0 0 0
2
µs
0 0 0 1
4
µs
…
…
…
…
…
1 1 1 0
30
µs
1 1 1 1
32
µs
Table 15. Minimum ON time
TON_MIN [6 … 0]
Time
0 0 0 0 0 0 0
0.5
µs
0 0 0 0 0 0 1
1
µs
…
…
…
…
…
…
…
…
1 1 1 1 1 1 0
63.5
µs
1 1 1 1 1 1 1
64
µs