background image

Ashby-P Insert 

15 

VENTING: DETERMINING MATERIALS 

 

 

TYPE OF MATERIALS:

 

 

1. PL Vent / Corn Vent must be used. 
 

2. All Joints in the venting installation must be fastened together using three screws. All joints of 
the venting system must be sealed with High Temp Silicone to make a gas tight fit. 

 

3. 

Exception:  Single  wall  stainless  steel  may  be  used  inside  an  existing  chimney. 

(No 

clearances to  combustibles are needed on single  wall stainless steel adaptors, rigid or  flex pipe 
installed within a chimney.) 

 

4.  A  clean  out  “tee”  has  been  built  into  the  Ashby.  This  cleanout  system  is  to  assist  in 
periodically cleaning the vent pipe. 

The exhaust system can periodically be cleaned from the 

inside of the unit without having to pull the unit from the fireplace. 

 

NOTE: ADHERE TO THE PL VENT CLEARANCES TO COMBUSTIBLES AS REQUIRED. 
STRICTLY OBSERVE THE PL VENT MANUFACTURER’S SAFETY SPECIFICATIONS. 

 

QUANTITY OF MATERIALS:

 

 

1.  It  is  recommended  that  the  vent  system  be  installed  with  a 

minimum  of  three  feet  (3’)  of 

vertical rise 

above the exhaust port on the back of the Ashby-P. 

 

FAILURE  TO  PROVIDE  THE  NATURAL  DRAFT  THAT  RESULTS  FROM  A  VERTICAL 
RISE  MAY  RESULT  IN  SMOKE  BEING  RELEASED  INTO  THE  HOUSE  WHEN 
ELECTRICITY  TO  THE  UNIT  IS  INTERRUPTED  WHILE  BURNING  OR  SMOLDERING 
FUEL REMAINS IN THE BURN GRATE. (

See “Battery Backup” on page 5) 

 

2.  It  is  not  recommended  to  run  vertical  venting  outside  the  heated  environment  where  the 
Ashby-P  is  installed.  Running  a  venting  system  in  a  cold  environment  may  cause  the  flue 
temperatures to cool down too much for adequate drafting.  

 

Additional vertical exhaust venting should be provided when using: 

 

a. More than one (1) elbow or tee; and/or 

 

b. Horizontal runs of over three (3) feet. 

(Horizontal runs over 10 feet not recommended)

 

 

3.  For  a  venting  system  ending  in  a  horizontal  run,  the  exhaust  pipe  must  be  terminated  by  a 
listed  end  cap  or  a  PL  vent  elbow  (45  or  90  degrees).  Note:  End  caps  or  elbows  must  vent 
exhaust gases away from the building. 

 

4. For termination above the building roofline a rain cap is required. 

 

5. The exhaust pipe on the Ashby-P is 3” O.D. to accommodate a pipe adaptor. 

Содержание Ashby-P Insert

Страница 1: ...ead this entire manual before installation and use of this pellet fuel burning room heater Failure to follow these instructions could result in property damage bodily injury or even death Contact local building or fire officials about restrictions and installation inspection requirements in your area ...

Страница 2: ...nting Typical PL Vent Components 14 Venting Determining Materials 15 Venting Termination Requirements 16 17 Venting Termination Clearance Requirements 18 Venting Installations 19 21 Outside Combustion Air 22 Mobile Home Installation 23 Ashby P Operation 24 Preventing Chimney Fires 24 Ashby P Approved Fuels 24 Installation Check 25 Ashby P Ashpan Locations 26 Control Board Features 27 28 Pre Lighti...

Страница 3: ...ol Pilot Settings 34 Diagnostic Features 34 35 Safety Features 35 Ashby P Maintenance 36 Versa Grate System 36 37 Daily Maintenance Versa Grate System 37 39 Periodic Maintenance 39 42 Yearly Maintenance 42 43 Safe Operation 43 Wiring Schematic 44 Troubleshooting Frequently Asked Questions 45 48 Ashby P Parts Breakdown 49 51 Warranty 52 Ashby P Info Notes 53 EMAIL support stcroixstoves com WEB ADDR...

Страница 4: ...emium pellets This insert is not intended as the sole source of heat EMISSIONS TESTING U S ENVIRONMENTAL PROTECTION AGENCY Certified to comply with 2020 particulate emission standards using pellet fuel Certified to the 2020 Phase of ASTM E2779 2010 Heat Output 7628 BTU hr 29916 BTU hr Efficiency 65 5 using the higher Heat Value of the Fuel Emission Rate 981 gr h SAFETY TESTING The Ashby P has been...

Страница 5: ... detrimental to exhaust systems Install the Stove with a minimum of the vent system exposed to the cold temperatures outside the envelope of the house BATTERY BACKUP St Croix does not offer battery backups They are available online if you decide to use one Battery backup systems are useful if the Stove is installed using horizontal venting only This prevents any smoke from entering your home in th...

Страница 6: ...til the odors disappear is recommended 7 The Stove will become HOT while in operation Keep clothing and furniture away from all hot surfaces 8 To avoid the possibility of smoke and or sparks entering the room always keep firebox and ash pan doors closed whenever the Stove is operating Smoke detectors installed in the same general area as the Stove may be activated if the Stove door is left open an...

Страница 7: ... the Ashby Series of inserts These systems are interchangeable in the stove body This Manual covers the Ashby P which uses the Versa Grate System burn system The Versa Grate System Is a Fully Automatic System that offers Self Ignition This system is approved for PFI Premium Pellets ...

Страница 8: ...Ashby P Insert 8 ASHBY P DIMENSIONS Figure 2 ...

Страница 9: ...10 C Top of Unit to Combustible Top Fascia Does not apply D Side of Unit to Combustible Top Fascia Does not apply Figure 4 The Hearth must extend a minimum of 6 152 mm in Front of Unit and beyond each side of the Fuel Loading and Ash Removal Opening s If the hearth is too short a non combustible Hearth Extension must be installed ...

Страница 10: ... N F P A 211 and any National State or Local codes that apply 2 In a Zero Clearance Fireplace The Factory built Zero Clearance Fireplace and its Chimney must be listed per UL 127 or ULC S610 standards 3 As a Zero Clearance Fireplace When building the unit in as a Zero Clearance Fireplace St Croix factory Built Cabinet part 80P54057 must be used Follow instructions on page 11 Figure 5 Minimum Firep...

Страница 11: ...d into the St Croix metal cabinet part number 80P54057 The cabinet must be installed on five 4x8x16 concrete blocks as shown in figure 6 above The framing dimensions listed above are based on using 4x8x16 block If raising the unit up higher factor the difference in height into the dimensions The cabinet allows for top and rear venting ...

Страница 12: ...urround panel Be sure to bolt the panel with the cord relief on the right hand side 3 Lay out the 3 piece trim kit and use the L Corner Brackets to attach the Trim kit together 4 Take the Trim kit and slide it down over the edges of the surround 5 Slide the assembled surround around the insert and in front of the fireplace opening Slowly slide the insert back and insert the side panels into the sl...

Страница 13: ...yder Simpson DuraVent and Selkirk Metalbestos and is carried by many local dealers In this manual approved venting will be referred to a PL vent or Single wall vent All single wall vent adaptors must be stainless steel NOTE TYPE B GAS VENT MUST NOT BE USED IN THE INSTALLATION OF THE ASHBY P INSERT Examples of venting system components follow High temperature ceramic roping reduces potential fly as...

Страница 14: ...VENT COMPONENTS RAIN CAP VERTICAL OR WALL THIMBLE CHIMNEY SUPPORT BRACKET HORIZONTAL ADAPTER ADJUSTABLE LENGTH SINGLE TEE SINGLE REDUCTION DOUBLE TEE PIPE w TEE CAP TEE w TEE CAP w TEE CAP PIPE ADAPTER INCREASER 450 ELBOW 900 ELBOW ...

Страница 15: ...nstalled with a minimum of three feet 3 of vertical rise above the exhaust port on the back of the Ashby P FAILURE TO PROVIDE THE NATURAL DRAFT THAT RESULTS FROM A VERTICAL RISE MAY RESULT IN SMOKE BEING RELEASED INTO THE HOUSE WHEN ELECTRICITY TO THE UNIT IS INTERRUPTED WHILE BURNING OR SMOLDERING FUEL REMAINS IN THE BURN GRATE See Battery Backup on page 5 2 It is not recommended to run vertical ...

Страница 16: ... Carports garage attic crawl space etc or any location that can build up a concentration of fumes 3 Vent surfaces can get hot enough to cause burns if touched by children Non combustible shielding or guards may be required The type of installation must first be considered before determining the exact location of the venting termination in relation ship to doors window cavities or air vents a Witho...

Страница 17: ...utside atmosphere and all flue gases are discharged to the outside atmosphere Special Venting Arrangements are listed in NFPA 211 31 10 7 1 2 The Vent Terminal of a Direct Vent Appliance with an input of 10000 BTU Hr or less shall be located at least 6 from any opening into a building and such an appliance with an input of over 10000 BTU Hr but not over 50000 BTU Hr shall not be located less than ...

Страница 18: ... BE AT LEAST 1 305 mm ABOVE the ground level 7 2 1 m FROM a public walkway 1 305 mm FROM The wall penetration point 3 915mm FROM a gas meter regulator assembly 2 610 mm FROM any adjacent combustibles such as Adjacent buildings fences protruding parts of the structure roof eaves or overhangs plants shrubs etc ...

Страница 19: ...rce for Outside Air Outside Air is Optional Outside combustion air may be recommended when certain conditions exist i e negative pressure A chimney system with known drafting problems may require a liner which may also need to be insulated to keep vent system warm in cold chimney environment ...

Страница 20: ... Page 20 Figure 12 Positive Connection to an existing Chimney with outside air optional The stove may be connected to an existing Class A chimney or a masonry chimney which meets the minimum requirements of NFPA 211 ...

Страница 21: ... Air for Combustion Masonry Fireplaces or as a built in Zero Clearance unit only ATTENTION We strongly recommend using a battery backup system if the stove is installed using horizontal venting only This prevents any smoke from entering your home in the event of a power failure ...

Страница 22: ...semi enclosed space Take care not to draw cold air past water pipes that may freeze 3 Increase the outside air pipe diameter to 3 for runs over ten 10 feet and elevation over 4 000 feet Note Long runs should be avoided 4 Terminate the outside air pipe below the exhaust vent outlet 5 An open mesh screen should be placed over the outside air pipe opening to prevent birds or rodents from nesting in t...

Страница 23: ...roix factory Built Cabinet part 80P53963 must be used Follow instructions on page 11 Mobile home installations must observe the following 1 WARNING DO NOT INSTALL IN A SLEEPING ROOM 2 WARNING COMBUSTION AIR MUST COME FROM THE OUTSIDE OF THE MOBILE HOME FAILURE TO DO SO MAY CREATE NEGATIVE PRESSURE WITHIN THE MOBILE HOME AND COULD DISRUPT PROPER VENTING AND OPERATION OF THE PELLET STOVE 3 CAUTION T...

Страница 24: ... and chimney connector should be inspected at least once every two months during the heating season to determine if a creosote build up has occurred If a significant layer of creosote has accumulated 3 mm or more it should be removed to reduce the risk of a chimney fire Use of an appropriately sized chimney brush or the services of a professional chimney sweep are recommended Also check to make su...

Страница 25: ...kes the pellets less slick that hard wood pellets INSTALLATION CHECK Proper installation is essential for safety effective Operation Warranty Coverage Insurance requirements and to meet Local Building Codes Installation Requirements are described in the first section of this manual Verify the installation is correct before firing up the Stove for the first time 1 The fans of this Stove may cause a...

Страница 26: ... ARE NOT DRAWN INTO AND CIRCULATED BY THE AIR CIRCULATION SYSTEM CLEANING OF THE HEAT EXCHANGER FLUE PIPE CHIMNEY AND DRAFT INDUCER IS ESPECIALLY IMPORTANT AT THE END OF THE HEATING SEASON TO MINIMIZE CORROSION DURING THE SUMMER MONTHS CAUSED BY ACCUMULATED ASH The Stove will not operate during a power failure Prolonged Power Outages will require the use of a generator to operate the Stove Ash Pan...

Страница 27: ...he Thermostat Mode and an LED Light bar that indicates which of the 5 Heat Settings the Stove is running on Figure 16 The LED Light bar is also used during the Diagnostic process see page 34 for more details 1 The Heat Level button will advance the setting up and down between level 1 and 5 It will also be used in the Fine Tuning process of the feed rates if needed See point 4 b 2 The Auger Feed bu...

Страница 28: ...ng when heating a small area or when Temperatures are Moderate c SmartStat Mode The unit is hooked to a Thermostat and when calling for heat the Insert will advance to the Heat level set at the Control board Once the Heat demand has been met the Insert will drop to the 1 Heat Level setting and pilot for one hour If the Thermostat does not call for heat during that hour the unit shuts off and re li...

Страница 29: ...he Versa Grate system Igniter installed and is for use with PFI Premium Pellets DO NOT USE THIS PROGRAM WITH THE ASHBY MF Program 4 is for adjusting for variations that occur with PFI Premium Pellets Ask your dealer before using this Program in your unit See page 25 for more information on variations between different brands of pellets Changing the program on the Control Board To change the Progra...

Страница 30: ...um switch locks in See Diagnostic features on page 34 and 35 b If the board senses the Vacuum switch the Combustion fan drops to the 1 setting and the Room fan shuts off c The Igniter and the Auger come on and feed for 1 5 minutes continuously and then switches to the 1 feed setting for the remainder of the ignition cycle d The stove will typically light in the first 3 4 minutes After 5 minutes th...

Страница 31: ...damper is correct However if the Stove needs cleaning changing the Damper may mask the fact that the stove is getting plugged It is always a good idea to thoroughly clean your stove before making a significant damper change If you experience problems adjusting the Stove during the Break In Period contact your dealer Some chimney systems will fall outside the norm for example a chimney with excessi...

Страница 32: ...y poor combustion not enough combustion air and should not be overlooked At the other end of the spectrum an extremely brisk flame which blows large pieces of live coal out from the Burn Pot area and causes stubborn shiny black build up on the glass too much combustion air is also considered undesirable and requires the damper to be closed Adjusting the damper during the break in period when burni...

Страница 33: ... feature of thermostatically controlling your new stove By using a thermostat to control the operation of your Pellet stove you can benefit two ways First of all after setting the thermostat to your desired heating needs the stove will operate accordingly to uniformly maintain your desired temperature setting Secondly the fuel consumption is being optimized which ultimately results in lowering you...

Страница 34: ...mbustion Fan voltage if needed Diagnostic Features of the Control Board The 2 LED 3 LED and 4 LED lights on the LED Light bar will flash to give a diagnostic code to help in diagnosing problems that may occur Read Frequently Asked Questions for more information These conditions fall into 2 categories a Heat related issues b Vacuum related issues The Diagnostic Lights flash as follows 1 The Proof o...

Страница 35: ...ive Simply wait until the cycle is complete Once the power light quits blinking and the board will respond again Safety Features 1 High Limit switch an overheat safety switch will shut off the fuel feed if the Insert reaches temperatures above normal operating temperature This is a Normally Closed switch If the High limit switch trips several times the problem in the Insert must be diagnosed befor...

Страница 36: ...ATE OF THE FUEL INCREASES NOTE FAILURE TO KEEP YOUR INSERT CLEAN AS DESCRIBED IN THIS MANUAL COULD RESULT IN POOR OPERATION INEFFICIENT FUEL USAGE AND A POSSIBLE SAFETY HAZARD IT IS THE RESPONSIBILITY OF THE OWNER USER TO DETERMINE THE NEEDED MAINTENANCE FREQUENCY CAUTION THE DOOR AND FRONT PART OF THE INSERT WILL BE HOT DO NOT TOUCH ANY PART OF THE UNIT THAT IS HOT The Versa Grate System Figure 2...

Страница 37: ... first operate your stove or whenever you change fuels check to determine needed cleaning frequency Daily Maintenance Ashby P CAUTION THE DOOR AND FRONT PART OF THE STOVE WILL BE HOT DO NOT TOUCH ANY PART OF THE STOVE THAT IS HOT CAUTION NEVER ADD FIRE STARTER TO A HOT STOVE 1 Check Grate Weldment and Shaker Plate See figure 22 on the following page to determine if holes are plugged Clean as neede...

Страница 38: ...hes that drop through the Shaker Plate Once this area gets plugged it will choke off the flow of Combustion Air to the Burn Pot causing the flame to be lazy The cover below the door is held in place with magnets Remove the cover to access the small Ashpan door Behind the door are 2 smaller ash pans used to remove the ashes that accumulate around the burn pot area in the fire box Figure 23 ...

Страница 39: ...aily with a cloth or paper towel will normally keep the window from accumulating difficult to clean residue Use of a glass cleaner ONLY permitted when the stove is cold Tip Dip the damp towel in the ashes to remove stubborn buildup on the glass CAUTION Do not slam the door Do not operate the stove with a broken or cracked glass Replace only with heat resistant ceramic glass supplied by the manufac...

Страница 40: ...ith a vacuum cleaner without having to pull the insert from the fireplace The Exhaust Tee Cleanout Rod must be pulled forward to open the Cleanout Tee Cleaning this area on a regular basis will prevent the vent system from becoming plugged with fly ash The recommended size of the hose to use for vacuuming this area is 1 25 outside diameter The hose should be inserted into the left Cleanout Port an...

Страница 41: ...uel being used See Figure 26 Clean the baffle on a regular basis Frequency of cleaning depends on amount of fuel being burnt and the quality of the fuel Fuel with low ash content is recommended Failure to clean the baffle can cause the Ashby P Insert to become plugged with fly ash To remove the baffle simply lift the baffle up off of the brick and remove from the insert Figure 26 ...

Страница 42: ...op condition Yearly maintenance is designed to assure safe operation prolong the life of the Ashby and help preserve its aesthetic appeal 1 Spring Shutdown After the last burn in the spring let the unit cool down Remove all fuel from the hopper and the auger Thoroughly clean the burn pot burn pot box ash pan and ash traps behind the ash pan To locate the ash traps see figure 24 2 The exhaust syste...

Страница 43: ...en up a fire in this heater Keep all such liquids well away from the heater while it is in use 3 Creosote Soot and Fly Ash Formation and Need for Removal The products of combustion will contain small particles of Fly Ash The fly ash will collect in the venting system and restrict the flow of flue gases Incomplete combustion such as occurs during start up and shut down or incorrect operation of the...

Страница 44: ... igniter running and approximately 2 Amp with out the igniter running The minimum recommended circuit is 15 Amp A dedicated circuit for the Insert is recommended CAUTION The electrical components of the Ashby P are not owner serviceable Call your dealer for proper diagnosis of electrical problems and service to those components ...

Страница 45: ...y leaks in these areas will negatively affect the burn process and cause the pot to overload 3 My Insert isn t burning and the number 2 LED light is blinking This diagnostic light indicates the vacuum switch no longer senses negative pressure in the firebox area of the Insert What caused the Insert to go out a The door of the unit was left open longer than 60 seconds See solution b The ash pan doo...

Страница 46: ...Insert down The Convection Blower could be defective or may need cleaning The high limit switch may be also defective It is best to call your dealer for support when trying to troubleshoot the High Limit Switch Do not use your Insert if the High Limit switch frequently trips 6 I turned the Insert on with the On Off switch and nothing happens First check to see if the Insert is plugged in and the r...

Страница 47: ...ecreasing the feedrates LED s 1 2 The ON time is increased or decreased 25 seconds with each adjustment Figure 29 9 Are there any adjustments that can be made through the control board to the Combustion Fan voltages to help adjust the draft Answer The Draft can be adjusted in a similar fashion as mentioned in the previous example The Fan voltages can be fine tuned while the Insert is in operation ...

Страница 48: ...SHBY MF Program 4 The Cycle Time is 10 seconds This Program offers Self Ignition and is only for units that have the Versa Grate system Igniter installed and is for use with PFI Premium Pellets DO NOT USE THIS PROGRAM WITH THE ASHBY MF Program 4 is for adjusting for variations that occur with PFI Premium Pellets Ask your dealer before using this Program in your unit See page 25 for more informatio...

Страница 49: ...ETSCREWS 3 80P52376 R CAM CONNECTOR ROD 4 80P53996 R SHAFT CAGE WELDMENT 5 80P52953 R VERSA GRATE BRACKET ASSEMBLY 6 80P50560 R CAM 7 80P52955 R REAR BUSHING ASSEMBLY 8 80P53914 R IGNITER TUBE WELDMENT 9 80P52727 R IGNITER 10 80P50553 R SPACER 11 98355A070 R COTTER PIN 12 80P52038 R SHAKER PLATE 13 80P53884 R GRATE WELDMENT 14 80P52954 R FRONT BUSHING ASSEMBLY 48 80P54123 IGNITER COVER ...

Страница 50: ... 80P20278 R AUGER MOTOR 24 80P30424 R MOTOR RETAINER BRACKET 25 80P50858 R AUGER WASHER 26 80P53666 R AUGER WELDMENT 27 80P30215 R BARB FITTING 28 80P52957 R MOTOR MOUNT BRACKET ASSEMBLY 29 80P20245 R AUGER GASKET 30 80P30459 R DAMPER ROD EXTENSION COLLAR 31 80P52630 R TERMINAL BLOCK 32 80P30368 R DAMPER INTAKE EXTENSION ROD 33 80P52628 R VACUUM SWITCH 34 80P30457 R VACUUM SWITCH BRACKET 35 80P304...

Страница 51: ... 49 80P30646 CERAMIC WOOL GASKET 50 80P30388 TUBE SCRAPER ROD 51 80P20175 BLACK END CAP 52 80P53885 ASH DOOR 53 80P53964 LOWER PANEL ASSEMBLY 54 80P53900 ASH PAN WELDMENT 55 80P53966 COAL RAKE ROD ASSEMBLY 56 80P30376 TRIM PLATE 57 80P53725 BAY DOOR BLACK COMPLETE 58 80P30463 LEFT DECORATIVE GRILL 59 80P53770 HOT AIR BOX W CLINCH STUDS 60 80P30599 STEEL BRICK PANEL RIGHT 61 80P30606 STEEL BRICK PA...

Страница 52: ...met the manufacturer s total responsibilities and liabilities shall be to repair or replace at the manufacturer s option the defective part s All costs of removal shipment to and from the dealer or manufacturer any losses during shipment and reinstallation and any other losses due to the Stove being removed shall be covered by the owner of the Stove NEITHER THE MANUFACTURER NOR THE SUPPLIERS TO TH...

Страница 53: ...Trim on the control board in the area below Draft Trim Circle one See point 4a on page 28 LED 1 LED 2 LED 3 LED 4 LED 5 Feed Trim Circle one See point 4b on page 28 LED 1 LED 2 LED 3 LED 4 LED 5 APPROVED FUEL PFI PREMIUM PELLETS PROGRAM Circle one see Figure 17 on page 29 3 4 Serial Number Date of Purchase Dealer Information ...

Отзывы: