You can see that the IP address of the device has been changed to "192.168.0.188" and the device name has been
changed to "sst-100"
4.5 IP Address Conflict Resolution
According to the specification of PROFINET protocol, acting as a PROFINET slave, GT200-PN-CO must obey
the rule that there can not be more than 1 PROFINET device which has the same IP address and Device name on
the same LAN when connecting many GT200-PN-CO devices.
If the IP address and device name conflict, users can change IP address and device name of GT200-PN-CO
according to
Chapter "4.4.2 Change IP Info and Name"
and make sure that other IP address and name are different
(Notes: after changing is complete, some relevant changes should be taken in PLC modeling and users must
ensure the IP address and name of GT200-PN-CO is the same with that of PLC modeling).
For example:
When IP address conflicts, the IP address, subnet mask and gateway address of GT200-PN-CO will be reset to
"0.0.0.0". Now, users can not use "Upload" or "Download" to scan GT200-PN-CO and only use
Scan Devices on LAN"
to scan the device, the scanning result is shown as below: