4
4 . Technical data
4 .1 Switch elements
Item name
EDI B7
SP-G-61-000-02
EDI B7B
SP-G-61-000-01
EDI C7
SP-G-61-000-04
EDI E1B
SP-G-61-000-05
EDI D1B
SP-G-61-000-09
Protection class (EN 60529)
IP 65
Protection class (EN 61140)
III
Operating ambient temperature
–25 … +70°C
Storage temperature
–25 … +80°C
Switch elements (EN 60947-5-1)
2 direct openings
2 direct openings
1 NO contact
Reset button
1 NO contact each
1 NO contact
Reset button
B10d value (EN ISO 13849-1)
250.000 switching cycles
MTTFd (mean time to failure, EN ISO 13849-1)
6849 (with switching frequency C = 1/d)
Electrical/mechanical service life (at +20°C)
Emergency stop buttons
Reset button
50.000 switching cycles (at rated load)
– 1 × 10
6
switching cycles
1 × 10
6
switching cycles
Max. bounce time
< 10 mS
Min. direct opening path
3 mm
Data according to UL508
Utilisation category (EN 60947-5-1)
DC13
DC13
Rated operating current Ie (EN 60947-5-1)
2 A
2 A
Rated operating voltage Ue 24 V DC (EN 60947-5-1)
24 V DC
24 V DC
Operating voltage
1 … 30 V DC
1 ... 36 V DC
Operating current
1 … 100 mA
1 ... 250 mA
Maximum switching capacity
250 mW
Housing material
PBT (polybutylene terephthalate)
Contact material
AgNi
AgNi, gold plated 5 µm
AgNi
Lighting connection emergency stop button
Operating voltage
max 30V AC / DC
Operating current
4 mA (-24V AC)
Lighting connection reset button, operating button
Operating voltage
max 30V AC / DC
Operating current
14 mA (at 24V DC)