8903/PB Profibus
Communications Interface

Technical Manual

HA469267U001  Issue 2

Compatible with 890 Firmware Version 1.4 onwards

Содержание 8903/PB

Страница 1: ...D Drives company without written permission from SSD Drives Ltd Although every effort has been taken to ensure the accuracy of this document it may be necessary without notice to make amendments or co...

Страница 2: ......

Страница 3: ...ent should be carried out by qualified personnel A qualified person is someone who is technically competent and familiar with all safety information and established safety practices with the installat...

Страница 4: ...Cont 4...

Страница 5: ...tep 1 Configuring the Profibus TechCard using DSE 890 10 Step 1 1 Inserting a PROFIBUS Function Block 10 Step 1 2 Attaching Fieldbus Connectors 11 Step 1 3 Configuring the Fieldbus Connectors 12 DSE D...

Страница 6: ...Contents Contents Page Cont 6...

Страница 7: ...installation Suitable for use with drive models 890CD Common Bus Drive and 890SD Standalone Drive using 890 firmware version 1 4 onwards LED s to indicate board and communications status Hardware soft...

Страница 8: ...rol Board 1 Remove the blank covers each secured by a single screw that fit over the TechCard holes 2 Loosen the top and bottom screws in the blue handles of the Control Board 2 3 Pull gently on the h...

Страница 9: ...trude through into the connector on the other side of the TechCard 2 Press the assembly into the TOP connector adjacent to terminals X10 X11 and X12 on the Control Board Ensure that the front panel of...

Страница 10: ...s into the slots Push until the back edge of the Control Board pcb locates with the connectors in the drive 2 Tighten in position using the top and bottom screws in the blue handles of the Control Boa...

Страница 11: ...d maintain this colour code throughout your network The cable has a single twisted pair with overall shielding The bus line is specified in IEC 61158 and it can be used in accordance with the table be...

Страница 12: ...N Red VP for termination only Pin Number PROFIBUS DP Cable Signal Meaning 1 Braid Shield Shield protective ground 3 Red B RxD TxD P Receive data transmission data positive 4 CNTR P Control signal for...

Страница 13: ...nodes from detecting any activity Connect terminating resistors to the end drives as shown below All resistors 5 minimum Watt Data line B 3 Data line A 8 GND 5 VP 6 390 220 390 Terminating resistors o...

Страница 14: ...0 OFF 2 2 21 0 OFF 3 4 22 0 OFF 4 8 23 0 OFF 5 16 24 0 OFF 6 32 25 1 ON 7 64 26 0 OFF 8 128 27 Node Address 0 255 0 OFF NA 32 Note Only addresses 1 to 125 are valid Profibus addresses LED Indications...

Страница 15: ...to ON the Address is set by the DSE 890 configuration A specific Address can be set using the DIP switches Refer to Setting Node Address page 8 If all the DIP switches are set to OFF i e the Address i...

Страница 16: ...g the Profibus TechCard using DSE 890 You can configure your Profibus TechCard using DSE 890 Follow the instructions below Step 1 1 Inserting a PROFIBUS Function Block Display your configuration page...

Страница 17: ...er Output FB Value Output Input connector the data is sent from PLC 890 Output connector the data is sent from 890 PLC The fieldbus connectors must be added before they will appear in the Profibus fun...

Страница 18: ...ts and Outputs trees to reveal the registers By default the trees each have one register To add more registers click on adjacent to New Note Note that once a register has been added it cannot be delet...

Страница 19: ...e front of the drive This is the default setting for Option Slot DSE Data Types Data Type Description Range LOGIC Logic False F and True T INTEGER 32 bit signed integer 2 147 483 648 to 2 147 483 647...

Страница 20: ...information about the Profibus network interface When online the actual Address in use can be found by clicking the right mouse button over the Address text and selecting Get This may be different to...

Страница 21: ...re to be used Click on Hardware 2 Import the GSD file for the 890 so that it appears in the Hardware Catalog Click on Options Install New GSD then use the file explorer to select the file ssd4890 gsd...

Страница 22: ...d 4 Configure which 890 registers are to be exchanged with the Master These are picked from the 890 in the Hardware Catalog window First click on the 890 icon in the Station window to open the registe...

Страница 23: ...FloatingPoint The matching module must be selected For example if Input Register 1 PLC Drive is declared as a Boolean in DSE 890 then the in 1 byte module must be selected 3 Fixed Parameters These ar...

Страница 24: ...Byte 0 1 2 3 4 5 6 7 Res erved Cmd Index Word Value 0 11 12 15 Bit Command Index 10 Sub Index Res erved Double Word Value Command The Command field in the request message selects the required operati...

Страница 25: ...These are listed in the GSD file in the DSE Configuration Tool or can be displayed on the MMI by holding the M key for a few seconds whilst displaying the parameter PREF Parameter Value or Error Code...

Страница 26: ...ange with watchdog response monitoring enabled Errors detected e g values from PLC out of range RED GREEN 50 RED 50 GREEN Data Exchange with watchdog response monitoring disabled Errors detected e g v...

Страница 27: ...se True From FLOATING POINT to LOGIC Zero Non zero False True From INTEGER 8 to LOGIC Zero Non zero False True From INTEGER 16 to LOGIC Zero Non zero False True From INTEGER 32 to LOGIC Zero Non zero...

Страница 28: ...32 bit IEEE floating point 2 147 483 648 to 2 147 483 547 Fractional part rounded Data from 890 Data to PLC From INTEGER to BOOLEAN Zero Non zero True False From INTEGER to FLOATING POINT 2 147 483 6...

Страница 29: ...UE 0 to 4 294 967 295 0 0 to 32 767 0 limits apply Data from 890 Data to PLC From VALUE to BOOLEAN Zero Non zero False True From VALUE to FLOATING POINT 32 768 0 to 32 767 9999 32 bit IEEE floating po...

Страница 30: ...MODIFICATION ECN No DATE DRAWN CHK D 1 Initial Issue HA469267U001 17320 03 06 05 CM KJ 2 Various small amendments 19213 15 02 06 CM KJ FIRST USED ON MODIFICATION RECORD 8903 PB Profibus Communications...