23
8903/PB Profibus Communications Interface
VALUE Type Connector
Data from PLC
Data to 890
From BOOLEAN to VALUE
False
True
0.0
1.0
From FLOATING POINT to VALUE
32-bit IEEE floating-
point
-32,768.0 to
32,767.9999
From INTEGER 8 to VALUE
-128 to 127
-128.0 to 127.0
From INTEGER 16 to VALUE
-32,768 to 32,767
-32,768.0 to 32,767.0
From INTEGER 32 to VALUE
-2,147,483,648 to
2,147,483,547
-32,768.0 to 32,767.0
limits apply
From UNSIGNED 8 to VALUE
0 to 255
0.0 to 255.0
From UNSIGNED 16 to VALUE
0 to 65,535
0.0 to 32,767.0
limits apply
From UNSIGNED 32 to VALUE
0 to 4,294,967,295
0.0 to 32,767.0
limits apply
Data from 890
Data to PLC
From VALUE to BOOLEAN
Zero
Non-zero
False
True
From VALUE to FLOATING POINT
-32,768.0 to 32,767.9999
32-bit IEEE floating-
point
From VALUE to INTEGER 8
-32,768.0 to 32,767.9999
-128 to 127
limits apply/
rounding applies
From VALUE to INTEGER 16
-32,768.0 to 32,767.9999
-32,768 to 32,767
limits apply/
rounding applies
From VALUE to INTEGER 32
-32,768.0 to 32,767.9999
-32768 to 32,767
limits apply/
rounding applies
From VALUE to UNSIGNED 8
-32,768.0 to 32,767.9999
0 to 255
limits apply/
rounding applies
From VALUE to UNSIGNED 16
-32,768.0 to 32,767.9999
0 to 32767
limits apply/
rounding applies
From VALUE to UNSIGNED 32
-32,768.0 to 32,767.9999
0 to 32767
limits apply/
rounding applies