Equalizing charging

 

    

Warning:

 risk of explosion! 

    In equalizing charging, an open lead-acid battery can produce explosive gas, therefore the 
battery chamber shall have good ventilation conditions. 
     

Note:

 risk of equipment damage! 

    Equalizing charging may raise the battery voltage to a level that may cause damage to sensitive 
DC loads. Check and make sure that allowable input voltages of all the loads in the system are 
greater than the set value for battery equalizing charging. 
     

Note: 

risk of equipment damage! 

    Overcharge or too much gas generated may damage battery plates and cause active material on 
the battery plates to scale off. Equalizing charging to an excessively high level or for too long a 
period may cause damage. Read carefully the actual requirements of the battery deployed in the 
system. 
Some types of batteries benefit from regular equalizing charging which can stir the electrolyte, 
balance the battery voltage and finish the electrochemical reaction. Equalizing charging raises the 
battery voltage to a higher level than the standard supply voltage and gasify the battery 
electrolyte. If the controller then automatically steers the battery into equalizing charging, the 
charging duration is 120 minutes (default). In order to avoid too much generated gas or battery 
overheat, equalizing charging and boost charging won’t repeat in one complete charging cycle.

Note:

   1) When due to the installation environment or working loads, the system can't continuously 
stabilize the battery voltage to a constant level, the controller will initiate a timing process, and 3 
hours after the battery voltage reaches the set value, the system will automatically switch to 
equalizing charging.
   2) If no calibration has been done to the controller clock, the controller will perform equalizing 
charging regularly according to its internal clock.
   

Floating charging 

   When finishing the sustaining charging stage, the controller will switch to floating charging in 
which the controller lowers the battery voltage by diminishing the charging current and keeps the 
battery voltage at the set value of floating charging voltage. In the floating charging process, very 
light charging is carried out for the battery to maintain it at full state. At this stage, the loads can 
access almost all the solar power. If the loads consume more power than the solar panel could 
provide, the controller will not be able to keep the battery voltage at the floating charging stage. 
When the battery voltage drops to the set value for returning to boost charging, the system will 
exit floating charging and reenter into fast charging. 

2. Product Installation

2.1 Installation Precautions

Be very careful when installing the battery. For open lead-acid batteries, wear a pair of goggles 
during installation, and in case of contact with battery acid, flush with water immediately. 
In order to prevent the battery from being short-circuited, no metal objects shall be placed near 
the battery. 
Acid gas may be generated during battery charging, thus make sure the ambient environment is 
well ventilated.  
Keep the battery away from fire sparks, as the battery may produce flammable gas.
When installing the battery outdoors, take sufficient measures to keep the battery from direct 
sunlight and rain water intrusion. 
Loose connections or corroded wire may cause excessive heat generation which may further melt 
the wire's insulation layer and burn surrounding materials, and even cause a fire, therefore make 
sure all connections are tightened securely. Wires had better be fixed properly with ties, and 
when needs arise to move things, avoid wire swaying so as to keep connections from loosening. 

When connecting the system, the output terminals' voltage may exceed the top limit for human 

safety. If operation needs to be done, be sure to use insulation tools and keep hands dry.  

The wiring terminals on the controller can be connected with a single battery or a pack of 

batteries. Following descriptions in this manual apply to systems employing either a single 

battery or a pack of batteries. 

Follow the safety advice given by the battery manufacturer.

When selecting connection wires for the system, follow the criterion that the current density is 

not larger than 4A/mm2. 

Connect the controller's earth terminal to the ground.

2.2 Wiring Specifications

  Wiring and installation methods must comply with national and local electrical specifications. 
  The wiring specifications of the battery and loads must be selected according to rated currents, 
and see the following table for wiring specifications: 

Model 

ML4860

Rated charging 
current 

Rated discharging 
current  

Battery wire 
diameter (mm2) 

 Load wire
 diameter (mm2)

Battery voltage 
compensation wire

60A 

20A 

>

15

<5

No requirements

2.3 Installation and Wiring

    

   Warning: 

risk of explosion! Never install the 

controller and an open battery in the same 

enclosed space! Nor shall the controller be 

installed in an enclosed space where battery gas 

may accumulate. 

    

  Warning:

 danger of high voltage! Photovoltaic 

arrays may produce a very high open-circuit 

voltage. Open the breaker or fuse before wiring, 

and be very careful during the wiring process. 

    

  Note: 

when installing the controller, make 

sure that enough air flows through the 

controller's radiator, and leave at least 150 mm of 

space both above and below the controller so as 

to ensure natural convection for heat dissipation. 

If the controller is installed in an enclosed box, 

make sure the box delivers reliable heat 

dissipation effect. 

150mm

Hot air

150mm

Cold air

Fig. 2.1 Installation and heat dissipation

5

6

!

!

!

Содержание ML4860

Страница 1: ...ual Model Battery voltage Max solar panel voltage Max input power Charging current Discharging current ML4860 12V 24V 36V 48V 150V 25 C 145V 25 C 800W 12V 1600W 24V 2400W 36V 3200W 48V 60A 20A Specifi...

Страница 2: ...ause damage Tips means advice or instruction for the operator Table of Contents 1 Product Introduction 1 1 Product Overview 1 2 Product Features 1 3 Exterior and Interfaces 1 4 Introduction to Maximum...

Страница 3: ...istorical data storage function is available and data can be stored for up to a year The controller is equipped with an LCD screen with which users can not only check device operating data and statuse...

Страница 4: ...t characteristic curve 1 5 Charging Stages Introduction As one of the charging stages MPPT can t be used alone but has to be used together with boost charging floating charging equalizing charging etc...

Страница 5: ...nstalling the battery For open lead acid batteries wear a pair of goggles during installation and in case of contact with battery acid flush with water immediately In order to prevent the battery from...

Страница 6: ...s be careful in operation First connect the battery then the solar panel and finally the load When wiring follow the order of first and then Power on After connecting all power wires solidly and relia...

Страница 7: ...current day Device information Bluetooth connection state This menu is available only to the display units with the optional bluetooth function Refer to Usage of Navigation Keys for operations includ...

Страница 8: ...DV over discharge BAT OVD over voltage BAT UVW under voltage warning L SHTCRT load short circuit L OVRCRT load over current internal over temperature battery over temperature solar panel overpower sol...

Страница 9: ...BstChgVol 9 0 17 0V 3 Floating charging voltage FltChgVol 9 0 17 0V Boost charging recovery voltage BstChgRev Over discharge recovery voltage LowVolRev Under voltage warning level UndVolWrn 4 Over dis...

Страница 10: ...the load mode setting 3 Press and hold in any menu but not the setting mode if the current load mode is manual mode pressing and holding the key will switch on off the load if the current load mode is...

Страница 11: ...value the load will cut off output after a time delay Load short circuit protection When the load is short circuited the controller can implement protection in a quick and timely manner and will try...

Страница 12: ...2V default 35 C to 45 C IP32 3 6kg RS232 RS485 3000m 285 205 93mm 5 2 Battery Type Default Parameters When selecting User the battery type is to be self customized and in this case the default system...

Страница 13: ...ion Efficiency 6 3 48V System Conversion Efficiency MPPT 24V conversion efficiency 24V battery 80 82 84 86 88 90 92 94 96 98 100 40 80 160 480 800 1200 1600 Output power W 40Vmp 60Vmp 80Vmp 90Vmp 110V...

Отзывы: