All-in-one solar charge inverter 9
Refer to the table below for recommended AC input wire diameter and switch:
Models
Recommended AC
input wiring diameter
Maximum bypass
input current
Recommended air switch or
circuit breaker type
HF4830S80-145
10mm2/7AWG
40A
2P—40A
HF4840S80-145
10mm2/7AWG
40A
2P—40A
HF4850S80-145
10mm2/7AWG
40A
2P—40A
HF4825U80-145
10mm2/7AWG
40A
2P—40A
HF4830U80-145
10mm2/7AWG
40A
2P—40A
HF4835U80-145
10mm2/7AWG
40A
2P—40A
Note:
There is already an appropriate circuit breaker at the Mains input wiring terminal, so it is
not necessary to add one more.
Recommended battery input wire diameter and switch selection
Models
Recommended
battery wiring
diameter
Rated battery
discharge
current
Maximum
charge
current
Recommended air
switch or circuit breaker
type
HF4830S80-145
30mm2/2AWG
85A
140A
2P—160A
HF4840S80-145
30mm2/2AWG
110A
140A
2P—160A
HF4850S80-145
30mm2/2AWG
125A
140A
2P—160A
HF4825U80-145
25mm2/3AWG
75A
120A
2P—140A
HF4830U80-145
25mm2/3AWG
85A
120A
2P—140A
HF4835U80-145
25mm2/3AWG
100A
120A
2P—140A