All-in-one solar charge inverter 10
Recommended AC output wiring specifications and circuit breaker selection
Models
Recommended
AC output
wiring diameter
Rated inverter
AC output
current
Maximum
bypass output
current
Recommended air
switch or circuit breaker
type
HF4830S80-145
10mm2/7AW
G
13A
40A
2P—40A
HF4840S80-145
10mm2/7AW
G
17.5A
40A
2P—40A
HF4850S80-145
10mm2/7AW
G
22A
40A
2P—40A
HF4825U80-145
10mm2/7AW
G
21A
40A
2P—40A
HF4830U80-145
10mm2/7AW
G
25A
40A
2P—40A
HF4835U80-145
10mm2/7AW
G
30A
40A
2P—40A
Note:
The wiring diameter is for reference only. If the distance between the PV array and the all-in-one
solar charge inverter or the distance between the all-in-one solar charge inverter and the battery is
relatively long, using a thicker wire can reduce the voltage drop to improve system performance.
Note:
The above are only recommended wiring diameter and circuit breaker. Please select the
appropriate wiring diameter and circuit breaker according to actual situations.