SMART CELLAR INVERTER COOLING UNIT
5. Remove the piezometer, open the liquid valve and gas valve completely using a spanner.
6. Tighten the screw caps of the valves and the refrigerant charging vent.
7. Reinstall the handle.
Leakage Detection
●
Leakage detection may be identified using a leak detector.
●
Dry nitrogen pressure test maximum allowable pressure 400psi if the outdoor system is
depleted of all refrigerants during repairs.
●
Alternatively, if a leak detector is not available, apply soapy water at the suspected position of
the leak. Observe over the course of approximately 3 minutes. Emerging air bubbles will
indicate the position of the leak, should one exist.
●
Alternatively, Vacuum check, pull a deep vacuum, 200 microns as a minimum for 30 min.
Test Operation
1. Turn the power on and press the ‘On / Off’ button on the remote controller.
2. Press the ‘Mode’ button to select Cool and Heat modes (if available) and check whether the
unit operates as expected.
NOTICE:
Please check the following after completing the installation.
Post Installation Checklist
●
Has the unit been installed correctly?
●
Has a refrigerant leakage test been performed?
●
Is the insulation of the drain pipe installed?
●
Does water drain well?
●
Is the electric wiring and piping installed correctly?
●
Is the unit grounded securely?
●
Does the power cord follow the specification?
WWW.AIRSHEPHERD.COM.AU
27