17
HX151K~601K
28
·
1 bar
Manual Reset
Table 3
DIMENSIONS AND CONNECTION SIZES
MODEL
DIMENSIONS
( mm )
INLET-OUTLET
CONNECTIONS
(PT, Male, inch)
H
W
D
HX76K / 101K
601 363
861 1
HX151K
601 363
921 1
HX201K / 251K
761 443
971 2
HX351K / 426K
811 493
1151 2
HX500K
811 493
1251 2
HX601K
811 543
1321
2
1/2
Table 4
DRYER SPECIFICATIONS
MODEL
RATED
CAPACITY
a
(N
/min)
POWER
SUPPLY
(V / PH/Hz)
WEIGHT
(kg)
INPUT
POWER
(kW)
REFRIGERANT
TYPE
b
HX76K
2.50 230/1/50
50
0.58 R134a
HX101K
3.00 230/1/50
53
0.60 R134a
HX151K
4.92 230/1/50
58
0.87 R-407C
HX201K
6.67 230/1/50
78
1.39 R-407C
HX251K
8.00 230/1/50
85
1.58 R-407C
HX351K
10.08 230/1/50
100
2.06 R-407C
HX426K
13.33 230/1/50
112
2.61 R-407C
HX500K
15.00 230/1/50
134
2.82 R-407C
HX601K
18.02 380~420/3/50
152
3.40
R-407C
a
Rating conditions are 35
inlet temperature, 7barg inlet pressure, 100% inlet relative humidity, 25
ambient temperature
@ 50Hz.
b
Refer to dryer data plate for refrigerant charge.
Table 5
DRYER OPERATING CONDITIONS
MODEL NO.
Maximum
Inlet Air
Pressure
Minimum
Inlet Air
Pressure
Maximum
Inlet Air
Temperature
Minimum
Inlet Air
Temperature
Maximum
Ambient Air
Temperature
Minimum
Ambient Air
Temperature
All models
16barg
3barg
49
4
43
4
Note : Continuous operation in the above maximum and minimum operating conditions is not allowable.
Goodnal STP ST041 Site Services (Jemaco HXK Series Refrigerated Air Dryers HX76K to HX601K Installation