5
b. Press ‘ESC’ at any time to return to the Main Menu.
NOTE: On dryers with air-cooled condensers, regular
condenser cleaning is recommended. Dirtiness
of ambient air at installation site will determine
frequency of service. Typically once a month is
recommended. Dryers contain an integral 3 micron
filter. As the filter element accumulates solid
contaminants, differential pressure increases. Solid
particulate load in the compressed air supply will
determine frequency of service. Typically element
changeout is recommended at least annually.
5. Push ESC button to exit program mode.
6. Manual Operation
a. To manually turn the refrigeration system on or off
use ‘On/Off’ button; Push ‘Schedule On/Off and
Enter’ button to return to schedule.
NOTE: After power interruption dryer will reenergize
in Manual override, refrigeration system off. To
restart Schedule: Push ‘Schedule On/Off and Enter’
button.
D.
Starting dryer
IMPORTANT: Dryer must be energized 24 hours before
starting refrigeration compressor.
NOTE: It is recommended that dryer be started 15 minutes
before compressed air flow begins.
1. On water-cooled models: after 24 hours, begin cooling
water flow.
2. Check for proper electrical voltage.
3. Slowly pressurize unit air side by opening inlet isolation
valve. Check for leaks.
4. After 15 minutes, open outlet isolation valve slowly.
5. Close air bypass valve.
6. Dryer may be operated in Manual or scheduled modes.
NOTE: Check for correct phasing of unit. On air-cooled
models: check fan rotation (air must be pulled through the
condenser). Fans may not start immediately or may cycle
on and off. If rotation is in the wrong direction follow the
procedure below. On water-cooled models: After starting
dryer if an unusual noise is heard and the discharge line
does not get hot, stop the dryer, reverse two power leads,
restart, and verify discharge line gets hot.
Manual
Mode - push On/Off button - refrigeration
compressor will start and run, green Compressor-on
light will illuminate. In this mode compressor will run
continuously and will not be turned on and off by the
monitor. MANUAL MODE will appear on interface panel.
Schedule
Mode - push Schedule On/Off and Enter
button. SCHEDULED MODE will appear on the interface
panel. The compressor will then turn on or off as
programmed.
NOTE: Dryer may be returned to the Manual Mode at
any time using the ‘Schedule On/Off and Enter’ button
or by pressing On/Off button. MANUAL MODE will appear
on interface panel. To reinstitute Schedule, push the
‘Schedule On/Off and Enter’ button again.
NOTE: Restart after the power interruption. Unit will be in
MANUAL MODE mode, refrigeration compressor, off when
power is restored after power interruption.
1. Temperature Indicator
2. Operator Interface Display
3. Power-on Light
4. Compressor-on Light
5. Alarm / Service Light
6. Schedule On/Off and Enter Button
a. In Display Mode: Press to toggle between
SCHEDULED MODE and MANUAL MODE.
b. In Program Mode:
i. Press to move to a lower level menu.
ii. Press to accept a value that has been edited.
7. Program Mode (i) and Esc
a. In Display Mode: Press and hold to enter Pro-
gram Mode.
b. In Program Mode: Press to move to a higher
level menu.
8. Up Arrow
a. In Display Mode: Press to cycle to next Display
screen
b. In Program Mode:
i. Press to view the next item in a list or to
increment a variable to a higher value.
ii. When the top of the list (or highest value) is
displayed, pressing the up button will cause
the display to wrap to the bottom of the list
(or lowest value).
9. Down Arrow
a. In Display Mode: Press to cycle to previous Dis-
play screen
b. In Program Mode:
i. Press to view the previous item in a list or to
decrement a variable to a lower value.
ii. When the bottom of the list (or lowest value)
is displayed, pressing the down button will
cause the display to wrap to the top of the
list (or highest value).
10. 1/0: Press at any time to turn the dryer on/off.
11. Drain test: Press at any time to momentarily open
the drains.
12. Reset: Press at any time to clear the alarm/service
message (if shown) and the alarm LED.
CONTROL PANEL
1
2
3
4
5
6
7
8
9
10
11
12