SPX FLOW Hankison HPR Series Скачать руководство пользователя страница 6

6

FIELD SERVICE GUIDE

Problems most frequently encountered with refrigerated dry

-

ers are water downstream of the dryer and excessive pressure 

drop. Most causes can be identified and remedied by following 

this guide.

    Closed  refrigeration  systems  are  potentially 

dangerous. Work on the refrigeration system must be done 

only by a competent refrigeration mechanic. Do not release 

fluorocarbon refrigerants to the atmosphere. All refrigerants 

must be recovered per EPA requirements. Do not smoke when 

a refrigeration leak is suspected. Burning materials may decom

-

pose refrigerants, forming a toxic gas or acids that may cause 

serious  injury  and  property  damage.  Before  dismantling  any 

part of the dryer or compressed air system, completely vent 

the internal pressure to the atmosphere.

PROBLEM

SYMPTOM

POSSIBLE CAUSE

REMEDY

Water Downstream of 

Dryer

Refrigerant compressor not 

running.

Leak in refrigeration system.

Contact your local distributor.

Compressor overheated.

Turn dryer off, wait 30 minutes; turn dryer on.  

(Motor thermostat self-starting)

Compressor burned out.

Contact your local distributor.

No condensate discharging from 

dryer.

Failure of drain.

Dismantle and clean strainer.  Repair or replace 

solenoid valve.

Dryer inlet air temperature too 

high.

Aftercooler malfunction.

Check aftercooler discharge temperature and 

reduce to dryer design condition (120°F max)

Excessive Pressure 

Drop Across Dryer

Low outlet pressure.

Dryer undersized (may also cause 

water downstream of dryer)

Check airflow and dryer capacity.  Reduce airflow or 

resize and replace dryer.

Dryer icing up. (check at separator)

Contact your local distributor.

Color Indicator Out of 

Green Zone

Indicator in red zone.

Inlet air temperature too high.

Reduce aftercooler discharge temperature to design 

conditions (See Engineering Data).

Condenser fouled or clogged.

Clean or replace condenser.

Inlet air temperature too high.

Reduce aftercooler discharge temperature to design 

conditions. (See Engineering Data)

High ambient temperature.

Ventilate area.

Improper adjustment of expansion 

valve.

Remove cap from the expansion valve and turn the 

screw until the indicator is in the green zone.

Indicator in blue zone.

Improper adjustment of expansion 

valve.

Adjust the expansion valve until the indicator is in 

the green zone.

Low ambient temperature.

Increase ambient temperature to design conditions.

Содержание Hankison HPR Series

Страница 1: ...rated Type Compressed Air Dryers Models HPR25 HPR35 HPR50 FOR M NO 7610 483 10 R EVI S ION 10 2015 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT I N...

Страница 2: ...nspected before leaving our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of...

Страница 3: ...stalled downstream of the refrigerated dryer The dryer will remove some entrained dirt extending the life of the replaceable filter element Outlet air temperature may be 10 to 30 degrees higher than i...

Страница 4: ...nty If problems arise during start up call your distributor Refer to Serial Number Tag for dryer operating capacity Do not exceed recommended capacity Drain connections must be made before the dryer c...

Страница 5: ...disassembly serious personal injury and valve damage may result 5 Remove screw and washer from front of the drain valve 6 Remove the power supply connector and gasket with the timer assembly if attac...

Страница 6: ...our local distributor No condensate discharging from dryer Failure of drain Dismantle and clean strainer Repair or replace solenoid valve Dryer inlet air temperature too high Aftercooler malfunction C...

Страница 7: ...peb R 134a R 134a R 134a a Rating conditions are 100 F inlet temperature 100 psig inlet pressure 100 inlet relative humidity 100 F ambient temperature 60Hz Per CAGI ADF 100 b Refer to dryer data plate...

Страница 8: ...8 ELECTRICAL SCHEMATICS ON OFF SWITCH WITH RUNNING LAMP R 2 5 6 PTC STARTER S M COMP 1PH C OVERLOAD PROTECTOR DRAIN SOL VALVE TIMER T Figure 1 25 50 scfm models...

Страница 9: ...e 2 25 50 scfm models HEAT EXCHANGER REHEATER AIR OUTLET AUX CONDENSER CONDENSER REF COMPRESSOR ELECTRONIC DRAIN VALVE LIQUID RECEIVER FILTER DRYER CONSTANT PRESSURE EXPANSION VALVE DRAIN OUTLET COLOR...

Страница 10: ...333 3163333 3163333 On Off Switch 3245021 3245021 3245021 Constant Press Expansion Valve 3161268 3161268 3161268 Liquid Receiver Filter Dryer 1283369 1283369 1283369 Electronic Drain Valve 3149293 314...

Страница 11: ...f the manufacturer s product The maximum damages liability of the manufacturer is the original purchase price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRAN...

Страница 12: ...kison americas spxflow com www spxflow com hankison Improvements and research are continuous at SPX FLOW Inc Specifications may change without notice ISSUED 10 2015 Form No 7610 483 10 Revision A COPY...

Отзывы: