SPX FLOW Hankison HPR Series Скачать руководство пользователя страница 3

Compressor

Oil Removal

Filter

Aftercooler

Automatic Drain

Dryer

Separator

Receiver

TYPICAL COMPRESSED AIR SYSTEM

INSTALLATION

Ambient Air Temperature

Locate the dryer indoors where the ambient air temperature will 

be between 40°F and 100°F. Intermittent operation at ambient 

temperatures up to 113°F will not damage the dryer but may 

result in a higher dew point or dryer shutdown due to high 

refrigerant discharge pressure (see Field Service Guide).
Do not operate air-cooled dryers at ambient air temperatures 

below 40°F. Such operation may result in low suction pressure, 

causing freeze-up.
Call  your  local  distributor  if  prolonged  operation  at  ambient 

temperatures above 100°F or below 40°F is unavoidable.

Location and Clearance

Mount the dryer on a level base. Install the dryer in a clean, 

well-ventilated area to reduce fouling of the condenser coils 

with dirt and dust.

Vapors and contaminants corrosive to copper and aluminum 

must not be in the area of the dryer or air compressor intake. 

Allow at least 6 inches clearance from the front and from the 

condenser coil service access. Install the dryer with the frame 

level. Anchor bolts are not required.

System Arrangement

Liquid water in the inlet air will adversely affect the performance 

of the dryer. Install the dryer downstream of an aftercooler or 

separator so that the temperature of the dryer inlet air does not 

exceed 120°F and the inlet air does not contain any liquid water.
Most compressed air systems require filters for removal of solid 

and liquid contaminants. When an oil-removal filter is used, it 

should be installed downstream of the refrigerated dryer. The 

dryer  will  remove  some  entrained  dirt,  extending  the  life  of 

the replaceable filter element. Outlet air temperature may be 

10 to 30 degrees higher than inlet air temperature. This is nor-

mal. Consult your distributor if a lower outlet air temperature 

is required.

Piping and Connections

Piping must be furnished by the user unless otherwise speci

-

fied. Connections and fittings must be rated for the maximum 

operating pressure given on the dryer data plate and must be 

in accordance with applicable codes. Support all piping; do not 

allow  the  weight  of  any  piping  to  stress  the  dryer  or  filters. 

Inlet and outlet shutoff valves and a bypass valve are recom

-

mended. Piping should be at least the size of the inlet and outlet 

connections to minimize pressure drop in the air system. See 

Engineering Data section for dryer inlet and outlet connections.

Removing Condensate

A separator with an automatic drain valve is supplied with each 

dryer. The user must install a separate discharge line at the drain 

connection to carry off condensate to an environmentally ap

-

proved condensate collection/disposal system. Securely anchor 

drain line to prevent whipping.

If clogging of the automatic drain is a problem, install a particu

-

late filter before the dryer to keep solid particles from entering 

the  dryer.  Contact  your  local  distributor  for  the  appropriate 

particulate filter.

Electrical Connections 

(See Figure 1)

Dryer is designed to operate on the voltage, phase and fre

-

quency listed on the serial number tag. Reference tag prior to 

making electrical connection. Dryers are supplied with a cord 

and plug. Install in receptacle of proper voltage.

  Operation  of  dryers  with  improper  line  voltage 

constitutes abuse and could affect the dryer warranty.

Содержание Hankison HPR Series

Страница 1: ...rated Type Compressed Air Dryers Models HPR25 HPR35 HPR50 FOR M NO 7610 483 10 R EVI S ION 10 2015 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT I N...

Страница 2: ...nspected before leaving our plant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of...

Страница 3: ...stalled downstream of the refrigerated dryer The dryer will remove some entrained dirt extending the life of the replaceable filter element Outlet air temperature may be 10 to 30 degrees higher than i...

Страница 4: ...nty If problems arise during start up call your distributor Refer to Serial Number Tag for dryer operating capacity Do not exceed recommended capacity Drain connections must be made before the dryer c...

Страница 5: ...disassembly serious personal injury and valve damage may result 5 Remove screw and washer from front of the drain valve 6 Remove the power supply connector and gasket with the timer assembly if attac...

Страница 6: ...our local distributor No condensate discharging from dryer Failure of drain Dismantle and clean strainer Repair or replace solenoid valve Dryer inlet air temperature too high Aftercooler malfunction C...

Страница 7: ...peb R 134a R 134a R 134a a Rating conditions are 100 F inlet temperature 100 psig inlet pressure 100 inlet relative humidity 100 F ambient temperature 60Hz Per CAGI ADF 100 b Refer to dryer data plate...

Страница 8: ...8 ELECTRICAL SCHEMATICS ON OFF SWITCH WITH RUNNING LAMP R 2 5 6 PTC STARTER S M COMP 1PH C OVERLOAD PROTECTOR DRAIN SOL VALVE TIMER T Figure 1 25 50 scfm models...

Страница 9: ...e 2 25 50 scfm models HEAT EXCHANGER REHEATER AIR OUTLET AUX CONDENSER CONDENSER REF COMPRESSOR ELECTRONIC DRAIN VALVE LIQUID RECEIVER FILTER DRYER CONSTANT PRESSURE EXPANSION VALVE DRAIN OUTLET COLOR...

Страница 10: ...333 3163333 3163333 On Off Switch 3245021 3245021 3245021 Constant Press Expansion Valve 3161268 3161268 3161268 Liquid Receiver Filter Dryer 1283369 1283369 1283369 Electronic Drain Valve 3149293 314...

Страница 11: ...f the manufacturer s product The maximum damages liability of the manufacturer is the original purchase price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRAN...

Страница 12: ...kison americas spxflow com www spxflow com hankison Improvements and research are continuous at SPX FLOW Inc Specifications may change without notice ISSUED 10 2015 Form No 7610 483 10 Revision A COPY...

Отзывы: