SPX Cooling Technologies Recold JW Series Скачать руководство пользователя страница 7

Recold 

/

 JW Series 

Fluid Cooler 

Selection Procedure

 

7

Closed circuit cooler selections can easily be made by using the information on pages 6 through 11. The 

examples below demonstrate proper procedures for water and ethylene glycol solutions. Other fluids can be 

cooled, but since their heat transfer and flow characteristics may vary, please contact your local Recold sales 

representative for assistance.

WATER SELECTION EXAMPLE

Select a unit to cool 225 GPM of water from 102°F to 

90°F at 76°F wet bulb temperature.

1.  Determine Range:

  102°F - 90°F = 12°F Range

2. Determine Approach:

  90°F - 76°F = 14°F Approach

3.  Select Load Factor — 

Enter Unit Load Factor Table 2  

for 76°F wet bulb. Select load factor based on 

12°F range and 14°F approach. Load factor in this 

example equals 3.3. When wet bulb temperature 

is an odd number interpolate between appropriate 

tables to determine the load factor.

4.  Select Unit Model — 

Table 3, the load factor 

determined in step 3 falls between 3.0 and 3.5. 

Enter the 3.0 column and read down to the smallest 

unit flow rating which is greater than or equal to 

225 GPM. For the Model JWL35B, interpolate 

between 245 and 190 GPM to determine the 

flow rating at the 3.3 load factor. Interpolation 

gives a rating of 212 GPM which is less than the 

design requirement. Select a Model JWL35C and 

again interpolate between load factor columns 

to determine flow rating. The second selection 

provides a flow rating of 245 GPM which exceeds 

the design requirement. The correct unit size is, 

therefore, a Model 35C

5.  Determine Flow Limitations — 

Enter Table 3 at unit 

size determined in Step 4 to select a JWL low flow 

or JW standard flow unit. The Model 35C with 225 

GPM design flow falls within the standard coil flow 

limitations. The correct unit selection is, therefore, 

a JW35C.

6.  Determine Coil Pressure Drop — 

Enter the Coil 

Pressure Drop Table at 225 GPM and read across 

to the unit model column to select pressure drop 

reading. In this example, pressure drop equals  

4.8 PSI.

ETHYLENE GLYCOL EXAMPLE

Select a unit to cool 75 GPM of 40% by volume 

ethylene glycol from 107°F to 85°F with 78°F wet 

bulb.

1. Determine Range:

  107°F - 85°F = 22°F Range

2. Determine Approach:

  85°F - 78°F = 7°F Approach

3.  Select Load Factor — 

Enter Table 2 for 78°F wet bulb 

and select load factor at design range and approach. 

Select 6.0 factor.

4.  Select Test Unit Model — 

Enter the Unit Rating 

Table 3 at the 6.0 load factor and read down to the 

smallest unit flow rating greater than or equal to the 

design 75 GPM. Select the test model JWL35C

5.  Correct Flow for Ethylene Glycol — 

The flow correction 

factor obtained from Table 1 is 1.04. 75 GPM x 1.04 

= 78 GPM

6.  Adjust Model Selection — 

Re-enter Table 3 at the 6.0 

load factor and make selection based on corrected 

flow of 78 GPM. The adjusted unit selection is the 

Model JWL50A indicating an 80 GPM rating

7.  Determine Flow Limitations — 

Enter Table 3 at unit 

size determined in Step 6 to select a JWL low flow 

or JW standard flow unit. The Model 50A with 

75 GPM design flow falls within the low flow coil 

limitations. The correct unit selection is, therefore, 

a JWL50A.

8.  Determine Coil Pressure Drop — 

For ethylene glycol 

pressure drop calculation, the conversion factor 

from Table 5 must be applied to design flow before 

entering Table 4. 75 GPM x 1.05 = 79 GPM. 

The coil pressure drop for 79 GPM is 2.4 PSI

DEFINITIONS

Range:

 the difference between the entering and 

leaving water temperatures (WT in – WT out).

Approach:

 the difference between the leaving water 

temperature and the web bulb temperature (WT out 

– WB).

Load BTUH

 =

GPM x 500 x Sp. Gr. x Sp. Ht. x (T

1

 – T

2

) where

Sp. Gr. = specific gravity at average temperature
Sp. Ht. = specific heat at average temperature
T

1

 = entering temperature

T

2

 = leaving temperature

Содержание Recold JW Series

Страница 1: ... Recold JW Series Fluid Cooler Engineering Data ...

Страница 2: ... coil can be drained without regard to internal corrosion This must be considered with steel tubes that do not have internal protection RECOLD HYDROSPRAY Recold engineering has developed an exclusive water distribution system called hydrospray This unique system provides optimum water coverage of the heat transfer coil for maximum efficiency and virtual elimination of harmful scale problems that r...

Страница 3: ...are constructed of PVC assemblies in removable easy to handle sections Each section has a three break design allowing three changes in air flow and measure approximately 5 inches in depth The use of durable PVC eliminates the corrosion problems associated with galvanized eliminators HEAT EXCHANGE COIL Coil tube bundle is constructed of 5 8 copper tubing with stainless steel tube sheets and copper ...

Страница 4: ...91 2 713 4 6 115 173 8 2 1 2 1 note 3 21 2 1 JW70 1841 4 981 2 931 4 192 47 191 2 841 2 8 115 note 4 2 1 2 1 note 3 3 11 4 JW85 208 981 2 933 8 217 47 191 2 961 2 8 1391 4 note 4 2 1 2 1 note 3 3 11 4 JW100 221 1181 2 1001 2 225 67 191 2 80 10 1391 2 note 4 2 2 2 2 note 3 4 11 4 JW115 2451 2 1181 2 1001 2 249 67 191 2 104 10 1641 2 note 4 2 2 2 2 note 3 4 11 4 JW130 269 1181 2 1001 2 273 67 191 2 ...

Страница 5: ...me gal JWH Coil Face Area sq ft Circuits Connection OD Circuits Connection OD Circuits Connection OD JW10A 10 2 2 5 8 43 21 2 2 5 8 16 9 7 JW10B 21 2 2 5 8 43 42 2 2 5 8 20 9 7 JW10C 21 2 2 5 8 43 42 2 2 5 8 24 9 7 JW15B 26 2 3 1 8 64 52 2 3 1 8 31 14 5 JW15C 26 2 3 1 8 64 52 2 3 1 8 37 14 5 JW25A 33 2 3 1 8 95 66 2 3 1 8 37 21 6 JW25B 33 2 3 1 8 95 66 2 3 1 8 47 21 6 JW25C 33 2 3 1 8 95 66 2 3 1 ...

Страница 6: ...at load on the coil at all time so that the leaving water temperature does not drop below 50 F Full flow alone will not protect the coil Temperature of 50 F must also be maintained Methods of maintaining the recommended fluid temperature may vary with system design and operation A simple means of preventing heat loss may be to locate the unit indoors allowing a heated atmosphere Adequate space and...

Страница 7: ...election is therefore a JW35C 6 Determine Coil Pressure Drop Enter the Coil Pressure Drop Table at 225 GPM and read across to the unit model column to select pressure drop reading In this example pressure drop equals 4 8 PSI ETHYLENE GLYCOL EXAMPLE Select a unit to cool 75 GPM of 40 by volume ethylene glycol from 107 F to 85 F with 78 F wet bulb 1 Determine Range 107 F 85 F 22 F Range 2 Determine ...

Страница 8: ...1 9 2 2 2 4 2 7 2 9 3 0 3 2 3 3 3 4 3 6 3 7 3 9 4 0 4 1 4 2 4 3 68 WET BULB RANGE 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 APPROACH 7 4 4 4 9 5 1 5 7 6 1 6 4 6 6 6 9 7 0 7 2 7 4 7 5 7 6 7 8 7 9 8 4 0 4 6 5 0 5 4 5 7 6 0 6 2 6 5 6 6 6 8 7 0 7 1 7 2 7 4 7 5 7 6 7 7 9 3 7 4 3 4 7 5 1 5 4 5 6 5 9 6 1 6 3 6 5 6 6 6 8 6 9 7 1 7 2 7 3 7 5 10 2 9 3 5 4 0 4 4 4 8 5 1 5 3 5 6 5 7 6 0 6 1 6 3 6 5 ...

Страница 9: ...8 2 9 3 0 3 2 3 3 3 4 3 5 3 6 3 7 3 8 30 1 1 1 4 1 6 1 8 2 0 2 2 2 4 2 5 2 7 2 8 2 9 3 1 3 2 3 3 3 4 3 5 3 6 3 7 80 WET BULB RANGE 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 APPROACH 7 2 9 3 5 4 1 4 5 4 8 5 1 5 4 5 7 5 9 6 1 6 2 6 4 6 6 6 7 6 8 7 0 7 1 7 2 8 2 7 3 3 3 8 4 2 4 5 4 8 5 1 5 3 5 5 5 7 5 9 6 1 6 2 6 4 6 5 6 6 6 8 6 9 9 2 5 3 0 3 5 3 9 4 3 4 5 4 8 5 0 5 2 5 4 5 6 5 7 5 9 6 1 6 ...

Страница 10: ...82 221 174 161 140 113 92 76 64 55 48 42 JWH 426 550 50A JWL 50 149 685 515 390 300 235 185 170 147 118 97 80 68 58 51 45 JW 150 550 50B JWL 50 149 JW 150 425 720 550 425 330 260 209 192 167 135 110 92 77 66 57 50 JWH 426 650 50C JWL 50 149 JW 150 425 760 585 455 355 281 225 207 181 147 121 101 85 72 63 55 JWH 426 650 70B JWL 70 209 JW 210 690 880 705 550 430 340 270 248 215 175 143 118 100 85 74 ...

Страница 11: ... 6 6 3 8 1 7 1 8 9 4 4 6 0 5 4 7 3 6 5 8 6 180 6 7 7 8 4 5 5 3 2 5 3 2 3 9 2 2 2 7 3 2 1 9 2 4 2 8 7 0 8 9 7 8 9 8 4 9 6 6 6 0 8 0 7 1 9 4 190 7 4 8 5 5 0 5 9 2 8 3 5 4 2 2 4 3 0 3 5 2 2 2 6 3 2 7 6 9 8 8 6 10 7 5 3 7 3 6 5 1 3 7 8 10 3 200 8 0 9 3 5 4 6 4 3 1 3 9 4 6 2 6 3 2 3 9 2 4 2 9 3 5 8 2 10 5 9 4 11 7 5 7 7 9 7 0 1 7 1 4 1 8 225 10 1 11 6 6 7 7 9 3 8 4 8 5 8 3 2 4 0 4 8 3 0 3 6 4 3 2 0 2 4...

Страница 12: ...r should be wired into the field control system to allow the dampers to fully open when the fan cycles on and close when the fan cycles off The actuator requires a 115V power supply ELECTRONIC WATER LEVEL CONTROL The electronic water level control package provides a constant and accurate means of monitoring water level in the unit For this reason it is often recommended for those installations whi...

Отзывы: