SPX Cooling Technologies Recold JW Series Скачать руководство пользователя страница 6

Recold 

/

 JW Series 

Fluid Cooler 

Freeze Protection

 

6

For the most part, evaporative closed circuit coolers 

will be installed for operation on a year-round basis. 

Units installed in a cold climate must be provided with 

adequate freeze protection for both the recirculating 

water and the heat exchange coil for proper 

equipment operation and maintenance.

RECIRCULATING WATER

The operation of evaporative cooled equipment under 

approximately full load conditions will prevent freezing 

of the recirculated water. However, during periods of 

very little or no heat load when fans and pumps are 

shut down, some form of freeze protection must be 

used.
A simple form of freeze protection commonly used 

is a remote sump tank inside a heated building 

below the evaporative cooled equipment. The water 

circulation pump is located at the remote tank 

circulating water through the evaporative cooler 

during load conditions. When the unit is shut down, 

the water drains down into the remote sump tank 

which is in a heated atmosphere.
The remote sump installation may be unacceptable in 

some cases due to unit location or space limitations. 

For these applications, pan water freeze protection 

may be attained by means of an optional electric 

heater located inside the unit pan. Electric pan 

heaters are designed to prevent pan water freezing 

during unit shut down with fans and pumps idle.
Water lines to and from the unit, pump, pump 

discharge and drain lines must be wrapped with a 

heat-tracing element and insulated to protect them 

from freezing.

HEAT EXCHANGE COIL PROTECTION

The best means of heat exchanger coil freeze 

protection is to circulate an ethylene glycol water 

solution. The solution freeze points with respective 

ethylene glycol by volume are given in Table 11 

below. This method will allow freeze protection 

irrespective of heat load or unit shut down.
Some applications will not permit the use of an 

ethylene glycol solution. Under these circumstances, 

other means of freeze protections must be used and 

the following rules strictly adhered to.
1. Maintain full flow through the coil
2.  Maintain heat load on the coil at all time so that the 

leaving water temperature does not drop below 

+50°F

Full flow alone will not protect the coil. 

Temperature of +50°F must also be maintained.

Methods of maintaining the recommended fluid 

temperature may vary with system design and 

operation. A simple means of preventing heat loss 

may be to locate the unit indoors allowing a heated 

atmosphere. Adequate space and ductwork must be 

provided for proper operation.
Units operating in low ambient conditions with a 

heat load which becomes very low or drops off 

completely may require the addition of an artificial 

load to maintain safe fluid temperature. The amount 

of artificial load required may be reduced by means 

of discharge positive closure dampers. The addition 

of the dampers will prevent induced air circulation or 

the chimney effect which may occur during unit shut 

down.
The above methods of coil freeze protection, when 

properly applied and maintained will provide good 

equipment protection. All methods, other than 

those using an adequate antifreeze solution, should 

provide a means of emergency coil draining. It is 

recommended that automatic drain valves and air 

vents with vacuum breakers be installed on each 

coil circuit. Adequately size drains with heat-tracing 

tape and insulation should be provided for free 

drainage. Should the circulating pump fail or the water 

temperature leaving the coil drop below 50°F for any 

reason, the coil will automatically drain preventing 

freeze damage.

Freeze 

Point

 

°F

Ethylene Glycol (by volume)

20%

30%

40%

50%

14

3

-14

-38

Unit Model 

JW/JWL

Ethylene 

Glycol 

By Volume

Design Flow 

GPM

40

50

70

90

100

125

150

175 Above

10A thru 35C

20%

1.07 1.05 1.02 1.00 1.00 1.00 1.00 1.00

1.00

30%

1.10 1.07 1.02 1.01 1.00 1.00 1.00 1.00

1.00

40%

1.14 1.11 1.05 1.01 1.00 1.00 1.00 1.00

1.00

50%

1.16 1.13 1.06 1.01 1.00 1.00 1.00 1.00

1.00

50A thru 50C

20%

1.12 1.09 1.05 1.03 1.02 1.00 1.00 1.00

1.00

30%

1.16 1.12 1.07 1.04 1.02 1.00 1.00 1.00

1.00

40%

1.19 1.16 1.11 1.06 1.04 1.01 1.00 1.00

1.00

50%

1.23 1.21 1.14 1.08 1.05 1.01 1.00 1.00

1.00

70B thru 130C

20%

1.15 1.11 1.09 1.06 1.04 1.03 1.01 1.00

1.00

30%

1.18 1.11 1.07 1.05 1.03 1.01 1.00

1.00

40%

1.20 1.15 1.10 1.07 1.05 1.03 1.00

1.00

50%

1.23 1.20 1.11 1.11 1.07 1.04 1.00

1.00

Table 1  Glycol Flow Correction Factors

Содержание Recold JW Series

Страница 1: ... Recold JW Series Fluid Cooler Engineering Data ...

Страница 2: ... coil can be drained without regard to internal corrosion This must be considered with steel tubes that do not have internal protection RECOLD HYDROSPRAY Recold engineering has developed an exclusive water distribution system called hydrospray This unique system provides optimum water coverage of the heat transfer coil for maximum efficiency and virtual elimination of harmful scale problems that r...

Страница 3: ...are constructed of PVC assemblies in removable easy to handle sections Each section has a three break design allowing three changes in air flow and measure approximately 5 inches in depth The use of durable PVC eliminates the corrosion problems associated with galvanized eliminators HEAT EXCHANGE COIL Coil tube bundle is constructed of 5 8 copper tubing with stainless steel tube sheets and copper ...

Страница 4: ...91 2 713 4 6 115 173 8 2 1 2 1 note 3 21 2 1 JW70 1841 4 981 2 931 4 192 47 191 2 841 2 8 115 note 4 2 1 2 1 note 3 3 11 4 JW85 208 981 2 933 8 217 47 191 2 961 2 8 1391 4 note 4 2 1 2 1 note 3 3 11 4 JW100 221 1181 2 1001 2 225 67 191 2 80 10 1391 2 note 4 2 2 2 2 note 3 4 11 4 JW115 2451 2 1181 2 1001 2 249 67 191 2 104 10 1641 2 note 4 2 2 2 2 note 3 4 11 4 JW130 269 1181 2 1001 2 273 67 191 2 ...

Страница 5: ...me gal JWH Coil Face Area sq ft Circuits Connection OD Circuits Connection OD Circuits Connection OD JW10A 10 2 2 5 8 43 21 2 2 5 8 16 9 7 JW10B 21 2 2 5 8 43 42 2 2 5 8 20 9 7 JW10C 21 2 2 5 8 43 42 2 2 5 8 24 9 7 JW15B 26 2 3 1 8 64 52 2 3 1 8 31 14 5 JW15C 26 2 3 1 8 64 52 2 3 1 8 37 14 5 JW25A 33 2 3 1 8 95 66 2 3 1 8 37 21 6 JW25B 33 2 3 1 8 95 66 2 3 1 8 47 21 6 JW25C 33 2 3 1 8 95 66 2 3 1 ...

Страница 6: ...at load on the coil at all time so that the leaving water temperature does not drop below 50 F Full flow alone will not protect the coil Temperature of 50 F must also be maintained Methods of maintaining the recommended fluid temperature may vary with system design and operation A simple means of preventing heat loss may be to locate the unit indoors allowing a heated atmosphere Adequate space and...

Страница 7: ...election is therefore a JW35C 6 Determine Coil Pressure Drop Enter the Coil Pressure Drop Table at 225 GPM and read across to the unit model column to select pressure drop reading In this example pressure drop equals 4 8 PSI ETHYLENE GLYCOL EXAMPLE Select a unit to cool 75 GPM of 40 by volume ethylene glycol from 107 F to 85 F with 78 F wet bulb 1 Determine Range 107 F 85 F 22 F Range 2 Determine ...

Страница 8: ...1 9 2 2 2 4 2 7 2 9 3 0 3 2 3 3 3 4 3 6 3 7 3 9 4 0 4 1 4 2 4 3 68 WET BULB RANGE 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 APPROACH 7 4 4 4 9 5 1 5 7 6 1 6 4 6 6 6 9 7 0 7 2 7 4 7 5 7 6 7 8 7 9 8 4 0 4 6 5 0 5 4 5 7 6 0 6 2 6 5 6 6 6 8 7 0 7 1 7 2 7 4 7 5 7 6 7 7 9 3 7 4 3 4 7 5 1 5 4 5 6 5 9 6 1 6 3 6 5 6 6 6 8 6 9 7 1 7 2 7 3 7 5 10 2 9 3 5 4 0 4 4 4 8 5 1 5 3 5 6 5 7 6 0 6 1 6 3 6 5 ...

Страница 9: ...8 2 9 3 0 3 2 3 3 3 4 3 5 3 6 3 7 3 8 30 1 1 1 4 1 6 1 8 2 0 2 2 2 4 2 5 2 7 2 8 2 9 3 1 3 2 3 3 3 4 3 5 3 6 3 7 80 WET BULB RANGE 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 APPROACH 7 2 9 3 5 4 1 4 5 4 8 5 1 5 4 5 7 5 9 6 1 6 2 6 4 6 6 6 7 6 8 7 0 7 1 7 2 8 2 7 3 3 3 8 4 2 4 5 4 8 5 1 5 3 5 5 5 7 5 9 6 1 6 2 6 4 6 5 6 6 6 8 6 9 9 2 5 3 0 3 5 3 9 4 3 4 5 4 8 5 0 5 2 5 4 5 6 5 7 5 9 6 1 6 ...

Страница 10: ...82 221 174 161 140 113 92 76 64 55 48 42 JWH 426 550 50A JWL 50 149 685 515 390 300 235 185 170 147 118 97 80 68 58 51 45 JW 150 550 50B JWL 50 149 JW 150 425 720 550 425 330 260 209 192 167 135 110 92 77 66 57 50 JWH 426 650 50C JWL 50 149 JW 150 425 760 585 455 355 281 225 207 181 147 121 101 85 72 63 55 JWH 426 650 70B JWL 70 209 JW 210 690 880 705 550 430 340 270 248 215 175 143 118 100 85 74 ...

Страница 11: ... 6 6 3 8 1 7 1 8 9 4 4 6 0 5 4 7 3 6 5 8 6 180 6 7 7 8 4 5 5 3 2 5 3 2 3 9 2 2 2 7 3 2 1 9 2 4 2 8 7 0 8 9 7 8 9 8 4 9 6 6 6 0 8 0 7 1 9 4 190 7 4 8 5 5 0 5 9 2 8 3 5 4 2 2 4 3 0 3 5 2 2 2 6 3 2 7 6 9 8 8 6 10 7 5 3 7 3 6 5 1 3 7 8 10 3 200 8 0 9 3 5 4 6 4 3 1 3 9 4 6 2 6 3 2 3 9 2 4 2 9 3 5 8 2 10 5 9 4 11 7 5 7 7 9 7 0 1 7 1 4 1 8 225 10 1 11 6 6 7 7 9 3 8 4 8 5 8 3 2 4 0 4 8 3 0 3 6 4 3 2 0 2 4...

Страница 12: ...r should be wired into the field control system to allow the dampers to fully open when the fan cycles on and close when the fan cycles off The actuator requires a 115V power supply ELECTRONIC WATER LEVEL CONTROL The electronic water level control package provides a constant and accurate means of monitoring water level in the unit For this reason it is often recommended for those installations whi...

Отзывы: