Specifications

Specification Value

Marley 

/

 

Sigma Steel 

Cooling Tower 

/

 

Specifications: Options

 

25

 

Oil Level Sight Glass:

5.4

   Replace paragraph 5.4 with the fol-

lowing:

 A galvanized oil gauge and 

drain line shall extend from the gear 

reducer to the vicinity of the motor, 

and shall be equipped with a bronze-

bodied oil level sight glass.

 

Miscellaneous Options

 

Steel Cold Water Basin:

10.1

   Replace paragraph 10.1 with the fol-

lowing:

 

Include a cold water collection 

basin constructed of 12 gauge hot-dip 
galvanized formed steel sheets. These 
sheets shall be bolted, gasketed and 
caulked to form a watertight basin 18" 
deep. A depressed, side outlet sump shall 
be included, having a 1/4" thick faceplate 
drilled for a standard 125# flange connec-
tion. An appropriately sized (3" diameter 
or larger) galvanized standpipe overflow 
shall be provided. The standpipe shall be 
removable for flush-out cleaning of the 
basin. A float-operated, mechanical make-
up valve shall also be included, installed 
adjacent to the endwall access door.

 

Factory Mutual Approval:

3.5

   Add the following paragraph in the 

Construction section:

 

The tower shall 

include all design and material modi-

fications necessary to meet the fire 

rating requirements of Factory Mutual. 

The product proposed shall be listed in 

the FM Approval Guide, latest edition.

 

Hot Water Basin Covers:

 

7.3

   Add the following paragraph to 

the Hot Water Distribution System 

Section:

 The distribution basins shall 

include galvanized steel covers. These 

covers shall be designed for a uniform 

live load of 40 psf, and shall be easily 

removable for maintenance.

 

Air Inlet Screens:

 

8.3

   Add the following paragraph to the 

Casing Section:

 The air inlet faces of 

the tower shall be covered by 1" mesh 

hot-dip galvanized welded wire screens. 

Screens shall be mounted in galvanized 

steel U-edging and shall be removable.

    The oil level sight glass is a convenience item that is preferred by many 

users. The same purpose is, of course, served by either the dip stick or 

the sight glass.

   Marley basins are used to permit the installation of towers on elevated 

platforms or foundations. 

 

This is the simplest of several cold water basin designs available for 

the Sigma Steel towers. Because of its bolted construction, it has the 

advantage of being hot-dip galvanized after fabrication. Marley can 

also install a 10 gauge welded stainless steel basin for a Stainless Steel 

Sigma. See 24.

■ 

   This could have a very beneficial effect 

upon your fire insurance premiums. 

Towers not able to meet FM require-

ments may require the inclusion of a fire 

protection sprinkler system to achieve a 

comparable level of insurance premium 

cost.

    These covers are designed to keep leaves and debris out of the circu-

lating water system. They also serve to suppress algae formation by 

shielding the incoming hot water from direct sunlight.

   In wooded or windy areas, these screens help to keep leaves or blow-

ing debris out of the cooling tower and circulating water system.

Содержание Marley Sigma Marley Sigma Steel

Страница 1: ...Marley Sigma Steel CoolingTower Engineering Data Specifications...

Страница 2: ......

Страница 3: ...m 18 Casing 18 Access 18 Cold Water Collection Basin 19 Scope of Work 19 Specifications Options Control Options Control System 20 Basin Heater 21 Fan Motor Variable Speed Drive 21 Marley Premium VFD S...

Страница 4: ......

Страница 5: ...rt of the continuing better ment of this Marley product line The Sigma Steel is a galvanized steel field erected general purpose crossflow cooling tower designed to serve normal air conditioning and r...

Страница 6: ...model indicates number of cells Change as appropriate for your selection Primary engineering data is per cell 3 Height shown is from base of tower columns to top of fan cylinder 4 Pumping head shown i...

Страница 7: ...ain at least 2 0 of clear space at tower endwalls for construction purposes Air inlet faces must have unobstructed air supply If obstructions exist nearby consult your Marley sales representative 4 Op...

Страница 8: ...r Marley sales representative 4 Minimum basin depth is 1 6 Basin depth may vary to suit your storage requirements 5 All anchor bolts complete with nut and washer must be furnished by others Bolts must...

Страница 9: ...required 4 Marley piping terminates at face of a cast iron flat face flange Bolt circle conforms to class 125 lb ANSI B 16 1 specifications 5 Supports on tower for crossover piping are part of the tow...

Страница 10: ...esigner must take care to provide generous air inlet paths and the tower s fan cylinder discharge height should not be lower than the elevation of the top of the enclosure Obtain a copy of Marley Tech...

Страница 11: ...u money in the long run both on operation and on maintenance Here are two of the more popular options Two Speed Motors Two speed motors improve operating flexibility by increas ing the number of poten...

Страница 12: ...ection that fits your space allot ment and whose power usage is acceptable Limitations on physical size and total operating horsepower avoid the introduction of unfore seen operational and site relate...

Страница 13: ...ase is incapable of performing as specified then you will not have received full value for your money Bear in mind that the size and cost of a cooling tower varies directly with its true thermal capab...

Страница 14: ...wind load and 5 g seismic load Framing joints shall be made with 1 2 diameter and larger Series 300 stainless steel machine bolts nuts and washers 3 4 Towers of more than one cell shall include galvan...

Страница 15: ...surance that the tower can withstand long term operation in a hostile environment but that it will accept many years of inspection and maintenance traffic by your operating personnel Fiberglass reinfo...

Страница 16: ...s a crossover pipe to deliver water to both sides of the tower 5 6 The mechanical equipment assembly shall be warranted for no less than five 5 years This warranty shall cover the fan s speed reducers...

Страница 17: ...parate external louvers used by others permit water to escape the fill and form ice or produce an unsightly situation adjacent to the tower If you plan to use your tower in the wintertime particu larl...

Страница 18: ...d steel shall also be provided 9 0 Access 9 1 There shall be a 33 wide by 61 high access door in each endwall casing to provide access to the interior of the tower Access doors shall be hinged and equ...

Страница 19: ...be responsible for the design fabrica tion and delivery of materials to the project site and for the erection of the tower over supports provided by others Unless otherwise specified all external pipi...

Страница 20: ...20VAC 50VA control power overload trip alarms and remote temperature control devices The temperature controller shall be adjustable for the required cold water temperature If a thermostatic controller...

Страница 21: ...drive shafts The VFD shall catch a fan spinning in the reverse direction without tripping The panel shall include a main discon nect with short circuit protection and external operating handle lockabl...

Страница 22: ...is no longer required The fluid cooler manu facturer shall supply VFD start up assis tance Tower vibration testing throughout the speed range is required to identify and lockout any natural frequency...

Страница 23: ...assure proper gear box lubrication the VFD sys tem shall de energize the motor once 25 motor speed is reached and cool ing is no longer required The VFD shall include de icing logic with auto canceli...

Страница 24: ...the ladder attached to the tower casing This extension shall be long enough to rise from the roof grade level to the base of the tower Anchorage and lateral bracing of the ladder extension shall be by...

Страница 25: ...r Distribution System Section The distribution basins shall include galvanized steel covers These covers shall be designed for a uniform live load of 40 psf and shall be easily removable for maintenan...

Страница 26: ...usually resolve these situations by using two speed motors in either 1800 900 or 1800 1200 RPM configuration and operating the fans at reduced speed without cycling after hours The natural nighttime r...

Страница 27: ...n in the tower Refer to our Stainless Steel Sigma Series in which the use of stainless steel has been maximized Except for valve bodies and Geareducer every steel component of that product line is man...

Страница 28: ...66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling T...

Отзывы: