Specifications

Specification Value

Marley 

/

 

Sigma Steel 

Cooling Tower 

/

 

Specifications: Base

 

19

9.2

 

The top of the tower shall be equipped 

with a sturdy 42" high guardrail sys-

tem, complete with top rails, interme-

diate rails and toeboards, conforming 

to OSHA standards. Guardrails and 

posts shall consist of 1.66" O.D. x 15 

gauge galvanized structural tubing. 

Posts shall be spaced on centers of 8'-

0" or less.

9.3

 

One endwall of the tower shall be 

equipped with a 20" wide aluminum 

vertical ladder, through-bolted to the 

endwall structure. Ladder shall rise 

from the cold water basin level to the 

top of the fan deck guardrail, and shall 

be designed and installed in confor-

mance with OSHA standards.

10.0

 

Cold Water Collection Basin

10.1

  The collection basin shall be heavy-

gauge galvanized steel and shall 

include the number and type of suction 

connections required to accommodate 

the out-flow piping system shown on 

the plans. Suction connections shall be 

equipped with debris screens. A fac-

tory installed, float operated, mechani-

cal make-up valve shall be included. An 

overflow and drain connection shall be 

provided in each cell of the tower. The 

basin floor shall slope toward the drain 

to allow complete flush out of debris 

and silt which may accumulate.

11.0

 

Scope of Work

11.1

  The cooling tower manufacturer shall 

be responsible for the design, fabrica-

tion, and delivery of materials to the 

project site, and for the erection of 

the tower over supports provided by 

others. Unless otherwise specified, all 

external piping, pumps, controls, and 

electrical wiring will be outside the 

cooling tower manufacturer's scope of 

work.

tion, alerting you to a potential maintenance head-

ache.

   Good maintenance practice requires period-

ic access to the top of the tower to inspect 

the distribution basins, as well as the struc-

tural integrity of the fan deck, fan cylinder, 

and fan — especially the fan blade secur-

ing hardware. 

There are no induced-draft 

cooling tower designs that are immune to 

this need!

   For the comfort and safety of your operating personnel, the Sigma 

Steel tower includes a ladder and guardrail of the quality and design 

indicated — and we strongly recommend that you require it of all bid-

ders! Portable ladders and other "make-do" access means are inappro-

priate for equipment of this size and complexity. 

 

■ 

   This basic specification assumes that the tower will be erected over 

a concrete basin at grade level. If the tower is to be installed on an 

elevated supporting platform, the steel cold water collection basin indi-

cated on page 24 should be included in the specifications.

   Please be clear in your specifications and inquiry 

documents regarding the full scope of work 

expected. That will help assure that your 

bid comparisons will be made on as equal 

a basis as possible—and will help to 

avoid any misunderstandings during 

Содержание Marley Sigma Marley Sigma Steel

Страница 1: ...Marley Sigma Steel CoolingTower Engineering Data Specifications...

Страница 2: ......

Страница 3: ...m 18 Casing 18 Access 18 Cold Water Collection Basin 19 Scope of Work 19 Specifications Options Control Options Control System 20 Basin Heater 21 Fan Motor Variable Speed Drive 21 Marley Premium VFD S...

Страница 4: ......

Страница 5: ...rt of the continuing better ment of this Marley product line The Sigma Steel is a galvanized steel field erected general purpose crossflow cooling tower designed to serve normal air conditioning and r...

Страница 6: ...model indicates number of cells Change as appropriate for your selection Primary engineering data is per cell 3 Height shown is from base of tower columns to top of fan cylinder 4 Pumping head shown i...

Страница 7: ...ain at least 2 0 of clear space at tower endwalls for construction purposes Air inlet faces must have unobstructed air supply If obstructions exist nearby consult your Marley sales representative 4 Op...

Страница 8: ...r Marley sales representative 4 Minimum basin depth is 1 6 Basin depth may vary to suit your storage requirements 5 All anchor bolts complete with nut and washer must be furnished by others Bolts must...

Страница 9: ...required 4 Marley piping terminates at face of a cast iron flat face flange Bolt circle conforms to class 125 lb ANSI B 16 1 specifications 5 Supports on tower for crossover piping are part of the tow...

Страница 10: ...esigner must take care to provide generous air inlet paths and the tower s fan cylinder discharge height should not be lower than the elevation of the top of the enclosure Obtain a copy of Marley Tech...

Страница 11: ...u money in the long run both on operation and on maintenance Here are two of the more popular options Two Speed Motors Two speed motors improve operating flexibility by increas ing the number of poten...

Страница 12: ...ection that fits your space allot ment and whose power usage is acceptable Limitations on physical size and total operating horsepower avoid the introduction of unfore seen operational and site relate...

Страница 13: ...ase is incapable of performing as specified then you will not have received full value for your money Bear in mind that the size and cost of a cooling tower varies directly with its true thermal capab...

Страница 14: ...wind load and 5 g seismic load Framing joints shall be made with 1 2 diameter and larger Series 300 stainless steel machine bolts nuts and washers 3 4 Towers of more than one cell shall include galvan...

Страница 15: ...surance that the tower can withstand long term operation in a hostile environment but that it will accept many years of inspection and maintenance traffic by your operating personnel Fiberglass reinfo...

Страница 16: ...s a crossover pipe to deliver water to both sides of the tower 5 6 The mechanical equipment assembly shall be warranted for no less than five 5 years This warranty shall cover the fan s speed reducers...

Страница 17: ...parate external louvers used by others permit water to escape the fill and form ice or produce an unsightly situation adjacent to the tower If you plan to use your tower in the wintertime particu larl...

Страница 18: ...d steel shall also be provided 9 0 Access 9 1 There shall be a 33 wide by 61 high access door in each endwall casing to provide access to the interior of the tower Access doors shall be hinged and equ...

Страница 19: ...be responsible for the design fabrica tion and delivery of materials to the project site and for the erection of the tower over supports provided by others Unless otherwise specified all external pipi...

Страница 20: ...20VAC 50VA control power overload trip alarms and remote temperature control devices The temperature controller shall be adjustable for the required cold water temperature If a thermostatic controller...

Страница 21: ...drive shafts The VFD shall catch a fan spinning in the reverse direction without tripping The panel shall include a main discon nect with short circuit protection and external operating handle lockabl...

Страница 22: ...is no longer required The fluid cooler manu facturer shall supply VFD start up assis tance Tower vibration testing throughout the speed range is required to identify and lockout any natural frequency...

Страница 23: ...assure proper gear box lubrication the VFD sys tem shall de energize the motor once 25 motor speed is reached and cool ing is no longer required The VFD shall include de icing logic with auto canceli...

Страница 24: ...the ladder attached to the tower casing This extension shall be long enough to rise from the roof grade level to the base of the tower Anchorage and lateral bracing of the ladder extension shall be by...

Страница 25: ...r Distribution System Section The distribution basins shall include galvanized steel covers These covers shall be designed for a uniform live load of 40 psf and shall be easily removable for maintenan...

Страница 26: ...usually resolve these situations by using two speed motors in either 1800 900 or 1800 1200 RPM configuration and operating the fans at reduced speed without cycling after hours The natural nighttime r...

Страница 27: ...n in the tower Refer to our Stainless Steel Sigma Series in which the use of stainless steel has been maximized Except for valve bodies and Geareducer every steel component of that product line is man...

Страница 28: ...66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling T...

Отзывы: