When the use of industrial antifreeze solutions is not possible, the system
must be operated to meet both of the following conditions.
1. Maintain sufficient flow rate through the coil.
2. Maintain sufficient heat load on the process fluid. Fluid exiting the
coil must be maintained at or above 7°C. Cycling of the recirculation
pump should not be used to control process temperatures.
Draining the coil is not acceptable as a normal method of freeze
protection—draining promotes corrosion inside the coil tubes. Drain-
ing is acceptable in an emergency if the coil is not protected by an
antifreeze solution.
It is recommended that you discuss your freeze prevention options with
your local Marley sales representative.
Operation
Note
Model
Coil Volume
Liters
Model
Coil Volume
Liters
MHF702__061
246
MHF705__061
890
MHF702__081
322
MHF705__081
1192
MHF702__101
397
MHF705__101
1476
MHF702__121
473
MHF705__121
1760
MHF702__062
284
MHF705__062
1079
MHF702__082
379
MHF705__082
1438
MHF702__102
454
MHF705__102
1779
MHF702__122
568
MHF705__122
2139
MHF703__061
322
MHF706__061
1476
MHF703__081
435
MHF706__081
1893
MHF703__101
530
MHF706__101
2309
MHF703__121
644
MHF706__121
2744
MHF703__062
379
MHF706__062
1798
MHF703__082
492
MHF706__082
2309
MHF703__102
625
MHF706__102
2839
MHF703__122
757
MHF706__122
3350
MHF704__061
606
MHF707__061
1703
MHF704__081
795
MHF707__081
2196
MHF704__101
984
MHF707__101
2688
MHF704__121
1173
MHF707__121
3180
MHF704__062
719
MHF707__062
2158
MHF704__082
946
MHF707__082
2801
MHF704__102
1192
MHF707__102
3426
MHF704__122
1420
MHF707__122
4054