Troubleshooting

Trouble

Cause

remedy

Geareducer noise. (If 
equipped).

Geareducer bearings

If new, see if noise disappears after one week of operation. Drain flush, 
and refill Geareducer oil. See Geareducer User Manual. If still noisy, 
replace.

Gears

Correct tooth engagement. Replace badly worn gears. Replace gears 
with broken or damaged teeth.

Unusual fan drive vibration

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment and 
supports.

Unbalanced drive shaft or worn couplings. (If 
equipped)

Make sure motor and Geareducer shafts are in proper alignment and 
"match marks" properly matched. Repair or replace worn couplings. 
Rebalance drive shaft by adding or removing weights from balancing 
cap screws. See Driveshaft User Manual

Fan

Make certain all blades are as far from center of fan as safety devices 
permit. All blades must be pitched the same. See Fan User Manual. 
Clean off deposit build-up on blades

Worn Geareducer bearings. (If equipped)

Check fan and pinion shaft endplay. Replace bearings as necessary.

Worn fan shaft bearings. (Belt drive).

Check fan shaft endplay. Replace bearings as necessary.

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates, rebalance 
rotor.

Bent Geareducer shaft. (If equipped).

Check fan and pinion shaft with dial indicator. Replace if necessary.

Fan noise

Blade rubbing inside of fan cylinder

Adjust cylinder to provide blade tip clearance

Loose bolts in blade clamps

Check and tighten if necessary.

Fan shaft bearing. (Belt drive).

Grease bearings.

Scale or foreign substance in 
circulating water system

Insufficient blowdown

See "Water Treatment" section of this manual.

Water treatment deficiency

Consult competent water treating specialist. See "Water Treatment" 
section of this manual

Cold water temperature too 
warm. 

See "Tower Operation."

Entering wet bulb temperature is above design

Check to see if local heat sources are affecting fluid cooler. See if 
surrounding structures are causing recirculation of tower discharge air. 
Discuss remedy with Marley representative.

Design wet bulb temperature was too low.

May have to increase fluid cooler size. Discuss remedy with Marley 
representative

Actual process load greater than design

May have to increase fluid cooler size. Discuss remedy with Marley 
representative

Overpumping

Reduce water flow rate over fluid cooler to design conditions.

Fluid cooler starved for air

Check motor current and voltage to be sure of correct contract 
horsepower. Repitch fan blades if necessary. Clean louvers, fill and 
eliminators. Check to see if nearby structures or enclosing walls are 
obstructing normal airflow to fluid cooler. Discuss remedy with Marley 
representative.

Excessive drift exiting fluid 
cooler

Distribution basins overflowing

Reduce water flow rate over fluid cooler to design conditions. Be sure 
distribution water basin nozzles are in place and not plugged.

Faulty drift elimination

Check to see that integral fill. Louvers and eliminators are clean, free of 
debris and installed correctly. If drift eliminators are separate from fill, 
make sure they are correctly installed and in place. Clean if necessary. 
Replace damaged or worn out components

Содержание Marley MH 05-116E

Страница 1: ...Marley MH Fluid Cooler User Manual 05 116E...

Страница 2: ......

Страница 3: ...n and operation of your fluid cooler Carefully read the manual before installation or operation of the fluid cooler and follow all instructions Save this manual for future reference Indicates presence...

Страница 4: ...te located on the access door Safety First The location and orientation of the fluid cooler can affect the safety of those responsible for installing operating or maintaining the fluid cooler However...

Страница 5: ...HF706 and MHF707 only Ladder extensions used where the base of the tower is elevated Safety cages for ladders External lube lines Access door platform Motor located outside the tower Double flow model...

Страница 6: ...fluid cooler from the delivering carrier inspect the shipment for evidence of damage in transit If damage is apparent note the freight bill accordingly This will support your future recovery claim Fi...

Страница 7: ...ooler to supporting steel with 3 4 diameter bolts and flat washers by others See support drawing for location and quantity Position flat washers between the bolt head and the fluid cooler basin flange...

Страница 8: ...sconnect switch the motor should be wired to main power supply through short circuit protection and a magnetic starter with overload protection Motor Wiring Wire motor leads as shown on the motor name...

Страница 9: ...limit amp draw to nameplate amps during cold weather operation If furnished with a mechanical O L set this at 110 over motor nameplate amps Motor rotation must be the same in both VFD mode and By pass...

Страница 10: ...ual Improper use of a VFD may cause damage to equipment or personal injury Failure to correctly install the VFD drive will automatically void all warranties associated with the motor and any equipment...

Страница 11: ...educer to the proper level with approved lubricant See Geareducer User Manual Check oil level at the Geareducer or dipstick standpipe located on fan deck if so equipped to confirm that the proper leve...

Страница 12: ...th a 2 minute time delay between changes of direction These delays will prevent abnormal stress from being applied to the mechanical equipment and the electrical circuit components 5 Run the motor and...

Страница 13: ...nue filling the system until the water reaches a level approximately 1 8 3 mm below the lip of the overflow 4 Start your pump s and check for proper rotation as indicated by the arrow on the pump cove...

Страница 14: ...7 0 to 7 6 The chlorine re sidual must be held at 4 to 5 mg L ppm for six hours measurable with standard commercial water test kits If the fluid cooler has been in operation and then shut down for a d...

Страница 15: ...e fluid cooler Reduced wet bulb temperatures will result in colder process fluid temperatures However the cold process fluid temperature will not vary to the same extent as the wet bulb For example a...

Страница 16: ...equipped with a two speed motor s you will enjoy greater opportunity for process temperature control When the process fluid temperature becomes too cold switching the fan to half speed will cause the...

Страница 17: ...he minimum allowable cold process fluid temperature is estab lished at or near minimum heat load it should be safe for all operat ing conditions Having established the minimum allowable cold water tem...

Страница 18: ...ive Caution note on page 12 for fan speed change and reversing precautions Intermittent Wintertime Operation If periods of shutdown nights weekends etc occur during freezing weather measures must be t...

Страница 19: ...r local Marley sales representative Operation Model Coil Volume US Gallons Model Coil Volume US Gallons MHF702__061 65 MHF705__061 235 MHF702__081 85 MHF705__081 315 MHF702__101 105 MHF705__101 390 MH...

Страница 20: ...led between 6 5 and 8 0 with hardness and alkalinity levels between 100 and 300 ppm expressed as CaCO3 Chlorine if used shall be added intermittently with a free residual not to exceed 1 ppm maintaine...

Страница 21: ...fill surfaces and the coil should be flushed by use of a moderate pressure water nozzle being careful not to cause physical damage A reliable water treatment program should be installed and maintaine...

Страница 22: ...ied hardware located at the top and bottom of the motor support assembly before adjusting the jacking screws Do not remove the hardware it is required to support the motor Tighten the hardware after a...

Страница 23: ...d of the rod next to the casing Turn the nut closest to the end of the rod to tighten the belt Turn the other nut to loosen the belt After achieving proper tension tighten the double nuts located on t...

Страница 24: ...ier Sheave Alignment The motor sheave is to be positioned as close as possible to the motor in order to minimize stress on the motor bushings The motor and fan sheaves may have grooves that are not us...

Страница 25: ...result in a fall Included with this instruction packet are separate User Manuals on each major operating component of the tower and it is recommended that you read them thoroughly Where discrepancies...

Страница 26: ...gh pressure water may damage the eliminator and louver material Observe operation of the float valve Depress the operating lever to make sure that the valve is operating freely Inspect the suction scr...

Страница 27: ...and fan guard Refer to Component User Manuals for torque values Inspect the fluid cooler thoroughly making maximum use of instructions given in the separate user manuals Check structural bolted conne...

Страница 28: ...draining promotes corro sion inside the coil tubes See protecting coil in Freezing weather on page 18 During shutdown clean the fluid cooler see Warning page 21 and make any necessary repairs Elimina...

Страница 29: ...Clean and lubricate motor at close of each operating season refer to motor manufacturer s recommendations Check motor anchor bolts and tighten as required See Page 28 for fluid coolers with motor loca...

Страница 30: ...e shipped within 24 hours by air freight if necessary However you would obviously benefit from anticipating your need in ad vance thus avoiding the cost of special handling Be sure to mention your flu...

Страница 31: ...x x Lube lines if equipped Check for oil leaks in hoses or fittings x R x Belt drive if equipped Fan shaft bearing lubrication every 3 mo every 3 months every 3 months Check and tighten support fasten...

Страница 32: ...nbalanced voltage Check voltage and current of all three lines against nameplate values Overload Check fan blade pitch See Fan User Manual Check for drag in fan drivetrain as from damaged bearings Wro...

Страница 33: ...haft bearing Belt drive Grease bearings Scale or foreign substance in circulating water system Insufficient blowdown See Water Treatment section of this manual Water treatment deficiency Consult compe...

Страница 34: ...eld installation is required for fan guards double flow models piping inlets and piping outlets Some optional accessories such as handrails ladders and safety cages may also require field installation...

Страница 35: ......

Страница 36: ...PARK KANSAS 66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008...

Отзывы: