4
operation and service
If lubricants other than Marley factory lubricants are used, they must
not contain any additives (such as detergents or EP additives) which
are adversely affected by moisture and could reduce the service
life of the Geareducer. The responsibility for use of lubricants other
than Marley factory lubricants rests with the customer/owner and
the lubricant supplier.
Note
—Geareducer is designed for 5-year oil change intervals.
To maintain five-year change intervals, use only Marley Gearlube.
Marley Gearlube must be inspected every six months to ensure
the oil has not been contaminated. If turbine-type mineral oil is
used the oil must be changed every six months.
Seasonal temperature changes may require one viscosity of oil for
summer operation and another for winter operation. Refer to the
tables below for the seasonal selection information.
Table 1
Synthetic oil—5-year oil change interval
Winter or Summer
Severe Duty/High Temperature
Air Temperature at Geareducer
Below 110°F (43°C)
Above 110°F (43°C)
ISO 150
ISO 220
R
– Refer to instructions within this manual
Note:
It is recommended at least weekly, that the general operation and condition be observed. Pay particular attention to any changes
in sound or vibration that may signify a need for closer inspection.
Maintenance Service
Monthly
Semi-annually
Seasonal Startup or Annually
Geareducer Drive
Inspect and tighten all fasteners including oil plug
x
x
Check for and repair oil leaks
x
x
x
Check oil level
x
R
x
Change oil
R
R
Make sure vent is open
x
x
Check driveshaft or coupling alignment
x
Inspect and tighten driveshaft or coupling fasteners
x
Check driveshaft or coupling bushing / flex elements for unusual wear
x
Lube Lines
(if equipped)
Check for oil leaks in hoses and fittings
x
R
x