Base:

 Furnish and install an induced-draft, crossflow, factory-

assembled, steel cooling tower of ____ cell(s), as shown 
on plans. Tower shall be similar and equal in all respects 
to Marley Series 4900 Aquatower, Model _______. Tower 
must be warranted by the manufacturer for one year from 
date of shipment.

Performance:

 Tower shall cool ____ m

3

/hr of water from ____ °C 

to ____ °C at a design entering air wet-bulb temperature 
of ____ °C and its thermal rating shall be certified by the 
Cooling Technology Institute.

Construction:

 Structural components of the tower, including 

the cold water basin, framework, mechanical equipment  
supports, casing, hot water basin, and fan cylinder shall 
be  fabricated  of  heavy-gauge  steel,  protected  against 
corrosion by Z-600 galvanizing per BS EN 10327:2004. 
All components subjected to factory welding shall be hot 
dip galvanized after fabrication per BS EN 150 1461:1999. 
Cold galvanizing is not acceptable.

Motor:

 Motor(s) shall be ____ kW, Totally Enclosed, specially  

insulated  for  cooling  tower  duty.  Speed  and  electrical 
characteristics shall be 1500 (or 1500/750) RPM, single-
winding, ____ phase, ____ hertz, ____ volts. The motor 
must  be  located  out  of  the  saturated  discharge  air 
stream.

Mechanical  Equipment:

  Fan(s)  shall  be  adjustable-pitch 

propeller type. Fan shall be driven through V-belt(s) with a 
minimum service factor of 1.5 based on full motor kW and 
protected with a belt guard. The fan and fan pulley shall 
be supported by oil lubricated tapered roller bearings in 
a cast iron housing with externally accessible remote oil 
reservoir for easy maintenance.

Fill,  Louvers  and  Drift  Eliminator:

  Fill  shall  be  film-type, 

thermoformed  PVC,  with  louvers  and  drift  eliminator 
formed as part of each fill sheet. Fill shall be suspended 
from hot dip galvanized structural tubing supported from 
the upper tower structure, and shall be elevated above 
the floor of the cold water basin to facilitate cleaning. Air 
inlet faces of the tower shall be free of water splash-out. 
Guaranteed drift losses shall not exceed 0.005% of the 
design flow rate. 

Hot Water Distribution System:

 An open basin above the fill 

bank  shall  receive  hot  water  piped  to  each  cell  of  the 
tower.  The  basins  shall  be  equipped  with  removable 
covers to keep out debris. This basin shall be installed and 
sealed at the factory. Water shall enter the basin through 
a  removable  wave-suppressor  splash  box.  The  basin 
shall be no less than 162mm deep to provide adequate 
freeboard against overflow and splash-out. Removable 
and replaceable polypropylene nozzles installed in the 
floor of the basin shall provide full coverage of the fill by 
gravity flow. Nozzles must all have the same orifice size 
and  be  spaced  symmetrically  in  both  longitudinal  and 
transverse directions.

Cold Water Basin and Accessories:

 The cold water basin shall 

be  factory  sealed.  For  maximum  installation  flexibility, 
basin  accessories  shall  include  both  a  side  suction 
connection and a hole and bolt circle in the basin floor 
suitable for gravity flow. Both connections shall include 
a  debris  screen  and  anti-cavitation  device.  A  factory-
installed, float-operated, mechanical makeup valve shall 
be included, having a 

3

4

" diameter inlet connection.

/  Specifications  /

Содержание Marley Aquatower

Страница 1: ...MarleyAquatower CoolingTower...

Страница 2: ...e all year long Proven Corrosion Protection Thousands of users over more than 40 years confirm the value of heavy galvanizing And Marley s Z 600 is the most effective galvanizing used in the industry...

Страница 3: ...r of local distributors can draw from that stock Contact your local distributor or Marley representative They ll be glad to help you choose the proper model for your needs They can also help you with...

Страница 4: ...et Install the desired connection and seal the unused opening with the cover plate provided Pump suction should use side outlet See page 9 for size and flow capacities of bottom outlets 7 Overflow is...

Страница 5: ...TION BASIN 16mm DIAMETER HOLES TOWER COLLECTION BASIN B NORMAL GAUGE MIN BEARING WIDTH AT EACH ANCHOR BOLT 51 SUPPORT BY OTHERS TOWER COLLECTION BASIN SUPPORTING STEEL PLAN OPTION ONE VIEW B SECTION A...

Страница 6: ...irborne trash out of the collection basin and fill area Hot water distribution basin covers are provided as standard equipment to keep the distribution basin free from airborne debris and to reduce th...

Страница 7: ...onsist of welded heavy gauge steel wire hoops and spokes hot dip galvanized after fabrication The galvanized steel belt guard encloses both belts and pulleys Guards are easily removed for servicing Co...

Страница 8: ...temperature dictates 5 Contact your Marley sales representative for selections appropriate for other ambient conditions than those shown here Indoor Tank Method In this type of system water flows from...

Страница 9: ...2 494A 494B 494C 13 6 32 507 32 3 51 5 549 51 7 85 4 613 85 6 127 8 674 495A 495B 18 6 43 6 689 43 8 61 3 727 61 5 116 5 829 116 7 173 3 912 496A 496B 23 6 44 5 863 44 7 64 9 920 65 1 112 8 1026 113 1...

Страница 10: ...stainless steel structure Or you can choose a galvanized tower with a stainless steel cold water collection basin Your Marley sales representative can help you choose the amount of corrosion resistanc...

Страница 11: ...housing with externally accessible remote oil reservoir for easy maintenance Fill Louvers and Drift Eliminator Fill shall be film type thermoformed PVC with louvers and drift eliminator formed as par...

Страница 12: ...BANK WORCESTER WR3 8AB UNITED KINGDOM 44 0 1905 720 200 info uk spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without noti...

Отзывы: