SPX Cooling Technologies MARLEY 07-1126 Скачать руководство пользователя страница 4

4

General Information

Description

The Marley Ultra Low-Noise series of fans represent the top in the 
new generation of super low noise fans—the FRP blades have been 
developed to meet the most stringent noise limitations. The fans 
permit variable pitch adjustment at standstill and feature a simplified 
design. Each blade is fixed to the hub with two bolted aluminum 
pillow blocks.

Balancing

When the rotor is dispatched in assembled form, each unit is dy-
namically balanced within a degree of G = 6.3 in accordance with 
ISO 1940/1.
When the fan is dispatched disassembled, the hub is dynamically 
balanced and the blades are statically balanced so that the reas-
sembled unit correspond to a degree of G = 6.3 in accordance with 
ISO 1940/1. In this case, the blades have the same static moment, 
so that they can be positioned in any order on the hub; the blades 
of the same supply, are interchangeable.

Storage

Upon unloading the fan, inspect it for any damage. If damage oc-
curred, file a claim immediately against the carrier and mark the bill 
of loading accordingly.
After the fan delivery, check the full compliance between order and 
delivered goods. Shortages or inconformities have to be reported 
within two weeks from receipt of shipment at destination.
If not installed immediately, it is recommended to store the fan in 
a dry and shaded area, and do not put any heavy materials of any 
kind upon the blades. For long-term storage, it is necessary to check 
the condition of the corrosion preventive coating on all machined 
surfaces.

Содержание MARLEY 07-1126

Страница 1: ...Marley Ultra Low Noise Fan User Manual 07 1126...

Страница 2: ......

Страница 3: ...3 Contents General Information 4 Installation 5 Operation 11 Maintenance 13 Parts List 16 Trouble Shooting 17...

Страница 4: ...mbled unit correspond to a degree of G 6 3 in accordance with ISO 1940 1 In this case the blades have the same static moment so that they can be positioned in any order on the hub the blades of the sa...

Страница 5: ...rmal direction of airflow as viewed from the discharge face of the rotor Installation Instructions 1 Remove blade pillow block and fasteners 4 5 6 7 15 from the hub disk one set a time Figure 2 2 If t...

Страница 6: ...6 Installation 10B 10A 1 5 9 3 7 2 6 10 4 8 Figure 2...

Страница 7: ...t into the drive shaft until it comes in contact with the drive shaft shoulder Drive the hub with cylindrical bore into the drive shaft until it comes in contact with the drive shaft shoulder or space...

Страница 8: ...Rotate fan to check tip clearance is in accordance with the specified value tip clearance ratio x D where x the distance from the blade tip to the fan ring and D the rotor diameter The gap between bla...

Страница 9: ...Figure 4 6 Repeat for each blade steps described in points 4 and 5 Before starting the pitch angle setting procedure turn the fan till the blade to be set is at the same point in the fan ring where p...

Страница 10: ...ta tion part list Stainless steel bolts 15 with the A4 80 stamping Fan Diameter inches Bolt 15 Bolt Torque N m ft lb 84 to 96 M18 175 6 129 108 to 120 M20 246 2 181 132 to 144 M24 425 7 313 In the cas...

Страница 11: ...irection of the blade rotation is cor rect see Rotation and Flow Direction Post Start Up 1 Check power absorption if excessive reduce the blade pitch angle until the desired power is achieved set the...

Страница 12: ...12 Operation 3 After the rotor has been running for one hour check the torque of the hub screws 15 4 Repeat the check of screws 15 after 24 hours from start up Figure 5...

Страница 13: ...Stop the unit completely before reversing the fan direction 6 Check the vibrations level in the position shown in Figure 5 at regular intervals The vibration level must not exceed the most restrictiv...

Страница 14: ...esonance between one of the possible forcing frequencies of the fan and one or more of the vibration modes of the structure on which it is installed The main forcing frequencies generated by the fan n...

Страница 15: ...bolts have to be tightened 11 The draining holes of the blades are obstructed they have to be opened The amplitude of the fan vibrations is determined by the rigidity of its support Vibration that wou...

Страница 16: ...Steel R40 HDG 10 Coupling Flange Nut Steel 8 8 class HDG 10A Space Ring if needed Steel Zinc Plated 10B Taper Bushing if required Malleable Cast Iron Burnished 11 Coupling Flange Bolt Steel 8 8 class...

Страница 17: ...17 Parts List 16 10B 10A 14 13 12 3 7 4 6 5 12 15 11 8 2 1 17 16 10 9 8 Figure 6...

Страница 18: ...e design Decrease blade pitch angle till 3 after checking the data sheet selection Rubbing between the blades and the fan ring Screws and bolts of the fan and or the structure loosened Torque all scre...

Страница 19: ......

Страница 20: ...RK KANSAS 66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2009 SPX...