Troubleshooting

Trouble

Cause

Remedy

Low air flow

Low power absorption

System congestion.

Clean the entire system.

Obstacles to the air flow.

Check the real obstacles area and the inlet shape towards 
the original design.

In dry-coolers the minimum free height of the inlet area has 
to be 1 time the fan diameter at least; this height has to be 
higher in case of multiple units in line.

Static  pressure  higher  than  the  specified 
one.

Increase  blade  pitch  angle  (till  3º  after  checking  the  data 
sheet selection.

Pitch  angle  lowered  by  blade  rotation 
(e.g.  screw  (15)  not  tightened  at  the  right 
torque).

Set the right pitch angle and refer to the operation manual 
to set the right torque of screws and bolts.

Temperature higher than the design.

Increase  blade  pitch  angle  (till  3º  after  checking  the  data 
sheet selection.

High power absorption

Temperature lower than the design.

Decrease blade pitch angle (till 3º after checking the data 
sheet selection.

Static pressure lower than the design.

Decrease blade pitch angle (till 3º after checking the data 
sheet selection.

Rubbing between the
blades and the fan ring

Screws  and  bolts  of  the  fan  and/or  the 
structure loosened.

Torque all screws and bolts.

Fan not centered.

Tip clearance too small.

Center the fan.

Increase the fan ring diameter.

High vibration level

Unbalance of one or more blades.

Contact SPX Cooling.

Blade  pitch  angle  not  included  in  the  0.5º 
tolerance.

Set right blade pitch angle.

Blades too close to supports (periodic aero-
dynamic turbulence).

Contact SPX Cooling.

Resonance  between  one  of  the  possible 
forcing  frequencies  of  the  fan  and  one  or 
more of the vibration modes of the structure 
on which it is installed.

Contact SPX Cooling.

Vibration  transmitted  by  the  structure  on 
which the fan is installed.

Contact SPX Cooling.

Resonance  of  the  blades  with  one  of  the 
possible forcing frequencies.

Contact SPX Cooling.

Misalignment of the drive shaft.

Realign of the drive shaft.

Worn output shaft bearing.

Contact the supplier.

The  fan  and/or  the  structure  bolts  are  not 
tightened.

Tighten screws and bolts at the right torque.

The  draining  holes  of  the  blades  are  ob-
structed.

Open the draining holes.

Содержание MARLEY 07-1126

Страница 1: ...Marley Ultra Low Noise Fan User Manual 07 1126...

Страница 2: ......

Страница 3: ...3 Contents General Information 4 Installation 5 Operation 11 Maintenance 13 Parts List 16 Trouble Shooting 17...

Страница 4: ...mbled unit correspond to a degree of G 6 3 in accordance with ISO 1940 1 In this case the blades have the same static moment so that they can be positioned in any order on the hub the blades of the sa...

Страница 5: ...rmal direction of airflow as viewed from the discharge face of the rotor Installation Instructions 1 Remove blade pillow block and fasteners 4 5 6 7 15 from the hub disk one set a time Figure 2 2 If t...

Страница 6: ...6 Installation 10B 10A 1 5 9 3 7 2 6 10 4 8 Figure 2...

Страница 7: ...t into the drive shaft until it comes in contact with the drive shaft shoulder Drive the hub with cylindrical bore into the drive shaft until it comes in contact with the drive shaft shoulder or space...

Страница 8: ...Rotate fan to check tip clearance is in accordance with the specified value tip clearance ratio x D where x the distance from the blade tip to the fan ring and D the rotor diameter The gap between bla...

Страница 9: ...Figure 4 6 Repeat for each blade steps described in points 4 and 5 Before starting the pitch angle setting procedure turn the fan till the blade to be set is at the same point in the fan ring where p...

Страница 10: ...ta tion part list Stainless steel bolts 15 with the A4 80 stamping Fan Diameter inches Bolt 15 Bolt Torque N m ft lb 84 to 96 M18 175 6 129 108 to 120 M20 246 2 181 132 to 144 M24 425 7 313 In the cas...

Страница 11: ...irection of the blade rotation is cor rect see Rotation and Flow Direction Post Start Up 1 Check power absorption if excessive reduce the blade pitch angle until the desired power is achieved set the...

Страница 12: ...12 Operation 3 After the rotor has been running for one hour check the torque of the hub screws 15 4 Repeat the check of screws 15 after 24 hours from start up Figure 5...

Страница 13: ...Stop the unit completely before reversing the fan direction 6 Check the vibrations level in the position shown in Figure 5 at regular intervals The vibration level must not exceed the most restrictiv...

Страница 14: ...esonance between one of the possible forcing frequencies of the fan and one or more of the vibration modes of the structure on which it is installed The main forcing frequencies generated by the fan n...

Страница 15: ...bolts have to be tightened 11 The draining holes of the blades are obstructed they have to be opened The amplitude of the fan vibrations is determined by the rigidity of its support Vibration that wou...

Страница 16: ...Steel R40 HDG 10 Coupling Flange Nut Steel 8 8 class HDG 10A Space Ring if needed Steel Zinc Plated 10B Taper Bushing if required Malleable Cast Iron Burnished 11 Coupling Flange Bolt Steel 8 8 class...

Страница 17: ...17 Parts List 16 10B 10A 14 13 12 3 7 4 6 5 12 15 11 8 2 1 17 16 10 9 8 Figure 6...

Страница 18: ...e design Decrease blade pitch angle till 3 after checking the data sheet selection Rubbing between the blades and the fan ring Screws and bolts of the fan and or the structure loosened Torque all scre...

Страница 19: ......

Страница 20: ...RK KANSAS 66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2009 SPX...

Отзывы: