Marley
/
MD
Cooling Tower
/
Engineering Data : Schematic
13
NOTE
1
Use this bulletin for preliminary layouts only
. Obtain current
drawings from your Marley sales representative. All table data
is per cell.
2 Last two characters of the model number indicate number of
cells and cell configuration. Change as appropriate for your
selection.
3 Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C
WB and .68 m
3
/hr per ton. The Marley
UPDATE
web-based
selection software provides MD model recommendations
based on specific design requirements.
4 Standard overflow is a 3"
dia. M connection located on the
side of the collection basin. Makeup water connection is 2"
dia.
M connection located on the side of the tower. A 3" M drain
connection is located on the side of the collection basin.
Model
note 2
Nominal Tons
note 3
Motor
kW
dBA
1.5m from air
inlet face
Dimensions
Design
Operating
Weight
kg
Shipping Weight
kg
H
A
Weight/Cell
Heaviest
Section
MD5010PAC2L
248
11
81
3628
2515
3906
2102
1052
MD5010PLC2L
249
11
80
MD5010QAC2L
269
15
81
MD5010QLC2L
270
15
80
MD5010RAC2L
286
18.5
81
MD5010RLC2L
289
18.5
80
MD5010PAD2L
279
11
81
3932
2820
4069
2265
1213
MD5010PLD2L
280
11
80
MD5010QAD2L
304
15
81
MD5010QLD2L
305
15
80
MD5010RAD2L
325
18.5
81
MD5010RLD2L
329
18.5
80
MD5010PAF2L
293
11
81
4237
3124
4256
2453
1376
MD5010PLF2L
294
11
80
MD5010QAF2L
317
15
81
MD5010QLF2L
318
15
80
MD5010RAF2L
341
18.5
81
MD5010RLF2L
346
18.5
80
MD5010SAF2L
360
22
81
MD5010SLF2L
362
22
81
MD5010 MULTICELL
Содержание Cooling Tower Marley MD