VOLTS

=  Nameplate Volts

  AMPS

=  Nameplate Amperage

  HP

=  Nameplate Horsepower

  DENSITY

=  Design Air Density

 

HP

=  Corrected Horsepower

  VOLTS

=  Actual Volts

  AMPS

=  Actual Amperage

  DENSITY

=  Actual Air Density

VOLTS

A

 

×

 AMPS

A

 

× 

DENSITY

D

VOLTS

N

 

×

 AMPS

N

 

× 

DENSITY

A

  

HP

 

=

× 

 HP

N

Note

Motor Load 

The corrected horsepower should be close to but not exceed the 
contract horsepower specified by SPX. Determine corrected horse-
power using the following equation.
Actual volts and amperage must be obtained with the fan running 
and the specified rate of water flowing over the tower after the motor 
and Geareducer have reached operating temperature (approximately 
30 minutes of operation).

Measurements taken on motors operating with Variable Fre-
quency Drive controls may read up to 15% high from errors in 
measuring the approximated sine wave. Instruments capable of 
measuring a squared off wave form accurately should be used 
for measuring power in this situation.
Do not exceed 30 sec/hour total motor starting time as motor 
may overheat.

Содержание COFIMCO 03-11A

Страница 1: ...Cofimco Fan Adjustable Hub User Manual 03 11A...

Страница 2: ..._______________________ Final Pitch Angle_ _________________________________ Speed rpm______________________________________ Contract hp______________________________________ Fan Components 101 104 V1...

Страница 3: ...king nut X12 Tighten 3 8 nut X12 to 40 ft lb 4 Position the blade clamp blocks 103 around the blade shank so that the blade 200 droops slightly downward when the blade clamp hardware is tight 5 Positi...

Страница 4: ...iving shaft extension for the full length of the key 3 Insert the key in the keyway The top of the key must be below the top of the shaft by not more than 1 8 3 mm The key is a tight fit across the wi...

Страница 5: ...e pitch is set 3 16 5 mm inboard of the blade tip by placing a protractor on top of a parallel sided straight edge that extends across blade width as shown in Figure 4 2 Be sure all blades are positio...

Страница 6: ...eration Remove any accumulated scale or dirt Clear blade drain holes at fan tip Service Proper identification of your fan is necessary to insure you receive correct replacement parts The Marley coolin...

Страница 7: ...wer using the following equation Actual volts and amperage must be obtained with the fan running and the specified rate of water flowing over the tower after the motor andGeareducerhavereachedoperatin...

Страница 8: ...6213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling Te...

Отзывы: