SPX Cooling Technologies COFIMCO 03-11A Скачать руководство пользователя страница 6

6

Fan Maintenance 

Preventative maintenance will prolong useful life and assure contin-
ued trouble-free operation.  After the first week and subsequently 
at six month intervals:
• Torque all hardware to specifications referenced in this manual.
•  Visually inspect the fan for airborne debris damage, contact with 
fan cylinder segments, and corrosive attack.  Correct any situations 
determined detrimental to fan operation.
• Remove any accumulated scale or dirt.
• Clear blade drain holes at fan tip.

Service

Proper identification of your fan is necessary to insure you receive 
correct replacement parts. The Marley cooling tower serial number 
can be used to determine the fan and any components installed and 
maintained as original equipment on a Marley cooling tower. Please 
provide the Marley sales representative the necessary information 
when ordering replacement fans or components.
Blades can be replaced without rebalancing the entire fan.
If rebalancing is desired, contact the Marley sales representative 
in your area.

Содержание COFIMCO 03-11A

Страница 1: ...Cofimco Fan Adjustable Hub User Manual 03 11A...

Страница 2: ..._______________________ Final Pitch Angle_ _________________________________ Speed rpm______________________________________ Contract hp______________________________________ Fan Components 101 104 V1...

Страница 3: ...king nut X12 Tighten 3 8 nut X12 to 40 ft lb 4 Position the blade clamp blocks 103 around the blade shank so that the blade 200 droops slightly downward when the blade clamp hardware is tight 5 Positi...

Страница 4: ...iving shaft extension for the full length of the key 3 Insert the key in the keyway The top of the key must be below the top of the shaft by not more than 1 8 3 mm The key is a tight fit across the wi...

Страница 5: ...e pitch is set 3 16 5 mm inboard of the blade tip by placing a protractor on top of a parallel sided straight edge that extends across blade width as shown in Figure 4 2 Be sure all blades are positio...

Страница 6: ...eration Remove any accumulated scale or dirt Clear blade drain holes at fan tip Service Proper identification of your fan is necessary to insure you receive correct replacement parts The Marley coolin...

Страница 7: ...wer using the following equation Actual volts and amperage must be obtained with the fan running and the specified rate of water flowing over the tower after the motor andGeareducerhavereachedoperatin...

Страница 8: ...6213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling Te...

Отзывы: