4.3
M
EASURE
O
F
D
ENSITY
It will be measured the density of the fluid contained in the tank.
LIGHTER SG
must be set to 0: alternatively to the selection of the Kg/l measurement
unit or the DENSITY transfer function, an error message will be displayed;
PV UNIT
must be set to Kg/l, or
XFR FUNCT
must be set to DENSITY;
LRV
must be set to the minimum density of the process liquid (default 0);
URV
must be set to the maximum density of the process liquid.
PV
will be the measurement of the
density of the process fluid expressed
in Kg/l.
The
LRV
value is the minimum density
of the process fluid and the URV is the
maximum density of the process fluid
to be set. In this mode it isn’t possible
to modify the values of
HEAVIER SG
and
LIGHTER SG
.
The
PV
will be the density of the fluid.
If the
LIGHTER SG
value is different
from 0 (measurement condition of
interface) it isn’t possible to pass at
the density measurement (selecting the
unit of measure Kg/l or the
XFR FUNCT
“Density”).
M
ANDATORY
!
To have this measurement available the displacer MUST BE completely immersed in
the process fluid. It must be selected kg/l as density measurement unit-