background image

11)

 

As the system continues to fill, the pump should resume operation. When the pump is running, water pressure at 
the outlet of the pump should be approximately between 20

-

35 psi. 

 

12)

 

During the fill operation if the water pressure does not exceed above 20 psi, ensure all the air vents are open. 

 

13)  Once all air is purged out of the system, the pressure at the pump outlet should remain steady. 

 

 
 
 

 
 

 
 

 
 
 
 
 
 
 

4.2 PROCESS FLUID DELIVERY 

 

Fluid delivery is accomplished via a jacketed pressure tank, jacketed valves, jacketed hoses, and a jacketed spray    
nozzle (s). 

 

The tank, is a pressure vessel that is pressurized with air to maintain a given setpoint at the nozzle location. 

 

1)

 

To ensure complete heating in every possible liquid delivery component, including the ball valves mounted on the 
tanks, are jacketed to maintain consistent heating. The hose delivering the fluid from the tank to the nozzles is 
completely jacketed. 

 

2)

 

Finally, the nozzles themselves are jacketed to maintain set temperatures. The tank is an ASME pressure vessel. 
The tank comes equipped with 125 psi safety valve, air regulator, and ball valves. 

 

3)

 

The main air supply goes into the inlet 2

-

way shut off valve. 

 

4)

 

Before opening the pressure tank, make sure the pressure in the system is relieved. 

 

 

Heated 
Water IN

 

Heated Water 
Pumped To 
Spray Nozzles

 

Recirculating 
Water From 
Pressure Tank

 

Supply water IN

 

Heated Water 
To Pump

 

Figure 4: Pump

 

Figure 5: Heater

 

Figure 6: Strainer

 

Process fluid inlet 
from tank

 

Process fluid 
outlet from tank 
to strainer

 

Heated Water

 

Figure 7: Fittings beneath Pressure Tank

 

Process 
fluid outlet

 

Heated Water 
Outlet

 

Process 
Fluid Inlet

 

Heated 
Water 
Inlet

 

Level Switch

 

Содержание AutoJet VC10

Страница 1: ...AutoJet VC10 Industrial Heated Spray System OWNER S MANUAL ML00VC10HTSYS spray com...

Страница 2: ...ning Control System Options 6 3 7 Spray Control Panel Options 7 4 Installing the System 8 4 1 Filling the Heating Loop 8 4 2 Process Fluid Delivery 9 4 3 Agitator And FRL Unit 10 5 System Start Up and...

Страница 3: ...r environment can be damaged or be in danger if the instructions are not followed correctly ATTENTION Supplementary information for the user that draws attention to possible problems SECTION 2 SAFETY...

Страница 4: ...ATTENTION Always remember to carefully read the chemical manufacturer s labels follow SDS and all directions WARNING OF SHOCK HAZARD To reduce the risk of electric shock do not open the cover on elect...

Страница 5: ...uminated Power On and Power off power pushbuttons and various illuminated selector switches A lockout disconnect switch is mounted on the door A low level indicator is illuminated when the tank is low...

Страница 6: ...tinuous liquid level sensor with auto refill addition Liquid outlet unit with manual 3 way ball valve for tank draining and 2 way ball valve for direct fluid line shut off Air motor driven liquid agit...

Страница 7: ...hes Terminal strips Cord grips for cable entry Figure 3 Digital Zone Control Optional Digital 8 zone control panel with or without timing control which includes the following components mounted into a...

Страница 8: ...the system Note that all the conditioning lines from the pump through all jacketed components and back to the return reservoir must be run in series Never split the flow path as this could result in c...

Страница 9: ...ponent including the ball valves mounted on the tanks are jacketed to maintain consistent heating The hose delivering the fluid from the tank to the nozzles is completely jacketed 2 Finally the nozzle...

Страница 10: ...es down to 5 microns in size CAUTION The agitator should never be operated without an oiled air supply Running without oiled air can result in a mechanical failure Providing more pressure to the agita...

Страница 11: ...ff 9 Open your valve on the air inlet to be in line with the regulator set your pressure regulator to the desired spray pressure and the tank will begin filling 10 Begin supplying air to your agitator...

Страница 12: ...3 SEQUENCE OF OPERATIONS General Information 1 Disconnect turned on 2 Operator powers system on 3 Operator opens air vents on the heating loop 4 Operator fills system with conditioning fluid water 5 O...

Страница 13: ...for liquid pressure tank Auto refill control box air operated Continuous liquid level sensor low level indicator for auto refill timer control box AUTO REFILL PROCEDURE 1 Connect power to the control...

Страница 14: ...e fluid level reaches 10 mm from the bottom of the probe 0 full the Low Tank Level indicator will turn on This is intended as a warning that the system is not automatically refilling The Low Tank Leve...

Страница 15: ...on procedures Pneumatic Connections Check all pneumatic connections for leaks and tighten Check system main air pressure as specified Tighten all screw terminal connections to insure proper bonding Ch...

Страница 16: ...switch to the ON position provide air to the auto refill pump to begin filling C When complete turn the auto refill switch to the OFF position to stop pumping D Repeat this process with appropriate f...

Страница 17: ...nector system should run No lights present insufficient water in the heating jacket loop or damaged sensor d Heater faulty or maximum temperature exceeded Press the EZ button on the heat controller to...

Страница 18: ...ion or design Other company and product names may be trademarks of their respective companies Warranty is one 1 year on non wear parts from ship date Wear items are covered for manufacturing defect on...

Отзывы: