background image

The hot gas or drained liquid bypasses the new nozzle position. In addition, the

liquid / vapor mixture flowing from the thermostatic expansion valve passes through

the extended nozzle. This tube eliminates any interference by hot gas entering

through the auxiliary connection with the flow from the thermostatic expansion

valve.

When an ASC is used to introduce hot gas to the evaporator inlet for capacity

control the distributor feed tubes generally should be one size lager than that

recommended for straight cooling duty - See table of Distributor Tube Circuit

Capacity - Tons, page 13, Bulletin 20-10 dated June, 1975. However, if the hot gas

bypass flow does not exceed the equivalent of 75% of the design cooling load then

tubes sized for straight cooling duty will be adequate.

FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY

© C

OPYRIGHT

1997 B

Y

S

PORLAN

V

ALVE

C

OMPANY

, W

ASHINGTON

, MO 63090

P

RINTED

I

N

U.S. 

OF

A.                                                                                                         F

ORM

SD-95-1-797  

Отзывы: