Sponsler SP714-S2i Скачать руководство пользователя страница 9

3-WIre TTL SOurCInG

The 3-wire TTL Sourcing configuration translates the output signal from the turbine flowmeter’s pickup coil into a 

voltage value. The output of the 3-wire TTL Sourcing configuration is driven either positive or negative internally. Note 

that the name “TTL” is misleading because the output switches from 0V to +Vs, not 0V to +5V as the TTL standard 

indicates. In the SP714-S2i, “TTL” indicates that the output is driven in both the positive and zero volt cases. A pull-

up or pull-down resistor is optional in the 3-wire TTL Sourcing configuration; however, a resistor can be installed to 

prevent damage from faults. 

To connect the SP714-S2i for 3-Wire TTL Sourcing:

1.  Remove the SP714-S2i housing cover.

2.  Pull the SP714-S2i board from the housing for access to the TB1 terminal block and the S1 switches.
3.  Attach proper cable glands and/or conduit connectors to the SP714-S2i, the pulse acquisition device, and DC power supply.

4.  Run the wires (through proper conduit) between the SP714-S2i, the pulse acquisition device, and DC power supply.

5.  Set the first S1 switch to the ON position and the second S1 switch to the ON position.
6.  Splice the resistor onto the +V 

leg from the DC power supply. 

This step is optional.

 

The value of the 

resistor can be determined using the 

information below.

7.  Wire the SP714-S2i to the pulse 

acquisition device and DC 

power supply as indicated in the 

schematic.

8.  If necessary, adjust the input 

signal sensitivity (R1), activate the 

diagnostic test oscsillator (SW2), 

and/or check the diagnostic 

operational LEDs (D1 & D2). 

See 

page 11.

9.  Coil the wires underneath the 

CPU board and place the board 

inside the housing, ensuring 

the wires are not pinched, and 

replace the housing cover.

3-WIre TTL SOurCInG WIrInG

S1

ON

ON

1 2

GND

  1

3 2 1

Signal

+V

0V

S1

Signal Ground

Position 1 - ON

Position 2 - ON

ON

ON

1 2

DC Power

Supply

Resistor (R

P

)

Electronic Register 

or 

Flow Computer

Chassis GND

Cable Shield

3 2 1

2 1

TB2

Pickup Coil Signal

TB1

INTERNAL OPERATING PRINCIPLE

optional

Three

Conductor

Shielded

Cable

Connect Chassis GNDs at pulse acquisition device only

sP714-s2i connections

Pulse Acquisition Device

Signal

Signal Ground

Sponsler IT 400

TB2 (

1)

TB2 (

2)

LectroCount 
LCR-II/LCR 600

J8 (

33)

J8 (

37)

Toptech MultiLoad

TB2B (V+ 

any)

TB2B (V COM 

any)

Maximum Cable Length: 

1000 m (3280’)

Minimum Wire Gauge: 

0.75 mm

2

 (18 AWG)

• 

Limit total system current to

 50 mA

   

I

max

 =

• 

For 24 VDC operation pulse acquisition device impedance must be at least 

1200 Ω

• 

For 5 VDC operation pulse acquisition device impedance must be at least 

250 Ω

• 

Resistor

 

(R

P

)

 

Power Dissipation

  

P =

Resistor Value - 3-wire TTL Sourcing

24 VDC Power Supply: 

R

p

 = 680 Ω, 1 W

12 VDC Power Supply: 

R

p

 = 330 Ω, 1 W

 5 VDC Power Supply: 

R

p

 = 12 Ω, 2.5 W

Recommended Resistor Value (R

p

)

V

dc

R

P

(V

)

2

R

P

9

Содержание SP714-S2i

Страница 1: ...Liquid Controls Group An IDEX Fluid Metering Business Sponsler SP714 S2i Pulse Amplifier Installation Parts Operation EM700 10...

Страница 2: ...strictly in the hands of the owner operators of the equipment Neglect of that responsibility is not within the control of the manufacturer NOTICE The most current English versions of all Liquid Contr...

Страница 3: ...fire department state and local codes to ensure adequate preparation Read this manual as well as all the literature provided in your owner s packet Save these instructions for future reference Failur...

Страница 4: ...40 to 176 F 40 to 80 C Storage 76 to 257 F 60 to 125 C Specifications Input Voltage 6 28 VDC 83 mA maximum 24 VDC Protected against polarity reversal Signal Input Frequency 2 kHz maximum over operatin...

Страница 5: ...y voltage Vcc 4 28 VDC Total System Resistance 500 minimum 28 VDC Output Voltage Logic HIGH Vcc 1 VDC Logic LOW 0 25 VDC Output Current Logic HIGH 8 to 60 mA DC Logic LOW 8 mA DC DC power supply volta...

Страница 6: ...eratures above 70 C use field wiring suitable for 20 C above maximum ambient temperature II Suitable for use in surface not mine installations 2 G High level of protection is provided against flammabl...

Страница 7: ...uration translates the output signal from the turbine flowmeter s pickup coil into a current value 2 wire connections are effective transmitting the signal over long distances The 3 wire TTL Sourcing...

Страница 8: ...llator SW2 and or check the diagnostic operational LEDs D1 D2 See page 11 9 Coil the wires underneath the CPU board and place the board inside the housing ensuring the wires are not pinched and replac...

Страница 9: ...using the information below 7 Wire the SP714 S2i to the pulse acquisition device and DC power supply as indicated in the schematic 8 If necessary adjust the input signal sensitivity R1 activate the di...

Страница 10: ...n the schematic 8 If necessary adjust the input signal sensitivity R1 activate the diagnostic test oscsillator SW2 and or check the diagnostic operational LEDs D1 D2 See page 11 9 Coil the wires under...

Страница 11: ...equency is above 40 Hz the light will flash very quickly and the LED will appear to be constantly illuminated If the input into the SP714 S2i stops on a positive portion of the signal pulse the LED wi...

Страница 12: ...rive Lake Bluff IL 60044 847 295 1050 SAMPI Via Amerigo Vespucci 1 55011 Altopascio Lucca Italy 39 0583 24751 IDEX Fluid and Metering Pvt Ltd Survey No 256 Alindra Savli GIDC Manjusar Dist Vadodara 39...

Отзывы: