Verification Signatures
Clearance
Checking
Date
Reason for test
14 mm ( ") wires Independent
or more
removed
assessor
- WARNING:
It is essential to remove the checking wires from the probe before
commissioning the boiler or vessel. Failure to do this could stop the low water alarms
operating.
-
The person who removes the checking wires must sign the record sheet to verify that this has
been completed.
- Independent assessor:
It is strongly recommended that an independent person (who might
be an Insurance Inspector, for example) verifies:
-
That the test has been carried out.
-
That the checking wires have been removed.
-
That the record sheet has been correctly completed by a competent person.