LCR2250 Level Controller
5.4 Meaning of codes on the 7-segment display
Valve open LED Amber
Valve closes LED Amber
MIN LED red
7-segment display
MAX LED red
Push buttons
Fig. 6
Code
Meaning
Indicated when up and down buttons are pressed:
AL.Hi
Alarm High
MAX switchpoint
adjustable between 0 and 100% measuring
range (see figure 7 opposite)
AL.Lo
Alarm Low
MIN switchpoint
SP
Setpoint
Setpoint
Pb
Proportional band
adjustable between 10 and 100 %
ti
Time integral
Integral action time, adjustable between 0 and 120 seconds
tt
Motor travel time
Valve travel time, adjustable between 10 and 600 seconds
tESt
Test
Tests output relays
FiLt
Filter
Used to dampen the effects of turbulent water level.
Indicated in parameterization mode
quit
Confirm
Input is not confirmed
done
Done
Input is confirmed
Indicated if malfunctions occur
E.005
Error
Faulty level transmitter, measuring current too low
E.006
Error
Faulty level transmitter, measuring current too high
E.013
Error
MIN switchpoint higher than MAX switchpoint