IM-P402-93 AB Issue 7
12
6.4 Level inputs - options
(All relays shown in the power off position)
Note: It is essential to select the correct sensitivity on the PA20 preamplifier,
(see the PA20 Installation and Maintenance Instructions for details).
+ Input
1 2 3
7 8 9
Fig. 9
PA20 preamplifier (0 - 6 V) input
(Links on preamplifier provide sensitivity
selection - see the preamplifier IMI for
more information).
+ Input
7 8 9
+ -
External power supply
18 - 30 V (nominal)
+ Input
7 8 9
+ -
-
+
Fig. 11
Externally powered 4 - 20 mA level
transmitter input
The earth terminal is internally connected to
the PA20 body, and earthed by the LP20
probe. Do not connect this earth terminal
to any other earths.
Fig. 10
Loop powered 4 - 20 mA input
(e.g. Two wire differential pressure transmitter)
4 - 20 mA transmitter wiring notes
1. Terminals 7, 5, 3 and 1 are linked inside the controller.
2. Terminal 8 provides loop power of 18 - 30 Vdc.
3. Input resistance between terminals 7 and 9 is 100
W
.
LP20 / PA20 wiring notes
1. Terminals 7, 5, 3 and 1 are linked inside the controller and are earthed via the
LP20 /PA20.
2. Terminal 8 provides a drive voltage 18 -30 Vdc.
3. Input resistance between terminals 7 and 9 is13 k
W
.
Maximum loop
resistance
750
W
Archive
Содержание LC2610
Страница 32: ...IM P402 93 AB Issue 7 32 To page 34 From page 30 To page 30 From page 34 A r c h i v e ...
Страница 33: ...IM P402 93 AB Issue 7 33 A r c h i v e ...
Страница 34: ...IM P402 93 AB Issue 7 34 MAXIMUM STEAM MAXIMUM STEAM MAXIMUM STEAM From page 32 To page 32 A r c h i v e ...
Страница 35: ...IM P402 93 AB Issue 7 35 ä To set up mode on page 19 or 23 ä To set up mode on page 19 or 23 A r c h i v e ...