IM-P402-93 AB Issue 7
11
6.3 Screen connection
To avoid damage to the product, screens must be installed as follows:
-
An earth current loop is created if a wire or screen is connected between two earth points,
which are at different potential (voltage).
-
The preamplifier and controller screen are only connected to earth at one end, i.e. at the
PA20 earth terminal.
Note: The PA20 earth terminal is a functional earth rather than a protective earth.
-
A protective earth provides protection from electric shock under a single fault condition.
-
This product has double insulation and therefore does not require a protective earth.
-
A functional earth is used in order for the product to operate.
-
In this application, the earth (tank /boiler shell) is used as the common of the probe / preamplifier.
-
It also provides a sink / drain for any electrical interference.
-
Ensure that the screen is connected to the common of the LC2610 (terminal 7) and to the
earth terminal of the PA20.
-
The LC2610 common terminal is internally isolated from earth.
-
The common terminal must only be earthed via the PA20.
CAUTION:
Do not connect the common terminals (1, 3, 5 and 7) to an earth local to the controller. To
do so may induce an earth current loop, which may reduce the performance or damage the
product.
Archive
Содержание LC2610
Страница 32: ...IM P402 93 AB Issue 7 32 To page 34 From page 30 To page 30 From page 34 A r c h i v e ...
Страница 33: ...IM P402 93 AB Issue 7 33 A r c h i v e ...
Страница 34: ...IM P402 93 AB Issue 7 34 MAXIMUM STEAM MAXIMUM STEAM MAXIMUM STEAM From page 32 To page 32 A r c h i v e ...
Страница 35: ...IM P402 93 AB Issue 7 35 ä To set up mode on page 19 or 23 ä To set up mode on page 19 or 23 A r c h i v e ...