6. Commissioning

The LC2400 has two channels; 'steam' and 'water', each channel consisting of a 4 -20 mA input
and a scaled output signal. To aid commissioning, each channel has a test input, which allows
measurement of the 4 - 20 mA signal without breaking the loop. See figure 5. The 'steam' channel
also has a range link, which selects one of two ranges to suit the anticipated rise in water levels.
In most cases, the link is fitted. See 'Steam flowmeter input' and figures 6 and 7.
Calibration is carried out by adjusting the 'steam' potentiometer on the LC2400. This raises the
control set point to match the rise in boiler water level at maximum steam demand.
For three element control using the LC2200 controller, the 'water' potentiometer is set to suit the
water flowmeter range.

Preferred  commissioning method Level probe input-
- Adjust the 'steam' potentiometer on the LC2400 to the zero position.

- Set the boiler water level (gauge glass) to the desired normal water level (set point).

- Adjust the LC2200 (or LC2300) set point potentiometer until the >50 % green LED just lights.

- Set the boiler water level to either the top or the bottom of the desired proportional band

(valve fully closed /fully open position), whichever is most convenient.

- Adjust the LC2200 (or LC2300) proportional band potentiometer until

the >100 % /<0 % amber LED just lights

The IM for the LC2300 gives further details of this procedure.

Steam flowmeter input
- Fit a wire link between terminals 4 and 5 of the LC2400.

- Alter the boiler water to the level anticipated when the steam demand is 100 %, i.e.

maximum steam flow.

- Adjust /program the steam flowmeter to output a  4 -20 mA signal representing 75 % of maximum

steam flow (usually 16 mA). See note below.

- Adjust the 'steam' potentiometer on the LC2400 until the green > 50% LED on the LC2200 /

LC2300 just extinguishes.

- Alter the water level to the set point (at zero steam flow).

- Adjust /program the steam flowmeter to output a signal representing 0 % of steam flow  (4  mA).

- Adjust the 'set point' potentiometer on the LC2200 / LC2300 until the green LED just lights.

Notes: If the green LED does not extinguish then remove the range link from terminals 4 and
5 then readjust the 'steam' potentiometer.
In use, the steam flowmeter output is 4 mA at zero steam flow, and 20 mA at maximum steam
flow. However, when we adjusted the LC2200/ LC2300 set point the steam input was
equivalent to zero output from the steam meter, not 4 mA. The steam flowmeter was set at 75%
output to compensate for this.

Содержание LC2400

Страница 1: ...ler Installation and Maintenance Instructions IM P402 84 AB Issue 6 4025950 6 Printed in the UK Copyright 1999 1 Safety 2 Application 3 Description 4 Installation 5 Wiring 6 Commissioning 7 Calibratio...

Страница 2: ...ystem uses an additional input from a water flowmeter to compensate for any variations in feedwater pressure 3 Description The Spirax Sarco LC2400 is used to connect a level controller to the4 20 mA o...

Страница 3: ...the LC2400 wiring The LC2400 is powered by the current loops 4 20mA andsoneedsnoseparatepower supply Figures 1to 4 pages 4 5 6 and 7 show the wiring connections for various applications Clamping screw...

Страница 4: ...ntrol relay Neutral Open Close Feedback input Feedback potentiometer 1 000 ohms Note Other actuators may have different connections Capacitance probe IN1 IN2 IN3 Connections to EL5600 series actuators...

Страница 5: ...ller Fig 2 Two element level control with pneumatic valve Pneumatic valve with positioner Steam meter LC2400 Level controller LC2300 Live For range link see commissioning instructions Range link Test...

Страница 6: ...o Feedback potentiometer is required Note Other actuators may have different connections Capacitance probe IN1 IN2 IN3 Connections to EL5600 Series actuators For link position and sensitivity see Prea...

Страница 7: ...12 2 3 1 4 20 mA current loop 1 2 3 4 5 6 7 8 9 10 11 12 4 5 6 1 3 LC2300 Level controller LC2400 Steam meter Level probe Steam Fig 4 Three element level control with pneumatic valve Feedwater LC2300...

Страница 8: ...ttom of the desired proportional band valve fully closed fully open position whichever is most convenient Adjust the LC2200 or LC2300 proportional band potentiometer until the 100 0 amber LED just lig...

Страница 9: ...or a maximum flow of 12 000 kg h The output current of the meter for this size of boiler is Output current 8 000 kg h x 16 4 14 67 mA 12 000 g h Calculate the water calibration value with the followin...

Страница 10: ...amplifier set to high sensitivity range link fitted Riseinwaterlevellessthan140mm PA20preamplifierset to mediumsensitivity rangelink fitted Preamplifier PA20 Medium sensitivity Preamplifier PA20 High...

Страница 11: ...e LC2400 and use figure 6 If the anticipated water level rise is greater than 80 mm and the PA20 is set to high sensitivity or greater than 140 mm and the PA20 is set to medium sensitivity do not inse...

Страница 12: ...nd Safety Executive Guidance Note PM5 For specific instructions for Spirax Sarco systems please see separate literature 9 Fault finding Green LED s not lit No supply from current loop present Loop con...

Отзывы: