Spirax Sarco LC2400 Скачать руководство пользователя страница 6

IM-P402-84  AB Issue 6

6

Note

 

on 4-20 mA loops:

Steam and water meter inputs (terminals

3 and 10) are earthed via the level probe.

Ensure any equipment connected to the

loop will operate with these terminals

grounded (earthed).

Steam meter

LC2400

Level controller LC2200

Live

Alarm

relay

Neutral

For range link
see commissioning
instructions

Range
link

Test

Control

 relay

Neutral

Open

Close

Note:

No Feedback

potentiometer

is required

Note:

Other actuators

may have different

connections

Capacitance

probe

IN1

IN2

IN3

Connections to

EL5600 Series

actuators

For link position
and sensitivity see
Preamplifier IM

2

3

4

5

6

7

8

9

1

10

11

12

2

4

1

2

3

1

4-20 mA
current
loop

4-20 mA
input

Set point output

+

-

1

2

3

4

5

6

7

+

8

9

10

11

12

13

17

18

19

+

14

15

16

LC2200 Level controller

LC2400

Steam meter

Level
probe

Steam

Motorised valve KE /EL

Fig. 3  Three element level control
           with electric valve

Make - up water

Water
meter

+

-

4-20 mA
current
loop

Water meter

Feedback input

0-8v 0utput

Live

Neutral

X5

Содержание LC2400

Страница 1: ...ler Installation and Maintenance Instructions IM P402 84 AB Issue 6 4025950 6 Printed in the UK Copyright 1999 1 Safety 2 Application 3 Description 4 Installation 5 Wiring 6 Commissioning 7 Calibratio...

Страница 2: ...ystem uses an additional input from a water flowmeter to compensate for any variations in feedwater pressure 3 Description The Spirax Sarco LC2400 is used to connect a level controller to the4 20 mA o...

Страница 3: ...the LC2400 wiring The LC2400 is powered by the current loops 4 20mA andsoneedsnoseparatepower supply Figures 1to 4 pages 4 5 6 and 7 show the wiring connections for various applications Clamping screw...

Страница 4: ...ntrol relay Neutral Open Close Feedback input Feedback potentiometer 1 000 ohms Note Other actuators may have different connections Capacitance probe IN1 IN2 IN3 Connections to EL5600 series actuators...

Страница 5: ...ller Fig 2 Two element level control with pneumatic valve Pneumatic valve with positioner Steam meter LC2400 Level controller LC2300 Live For range link see commissioning instructions Range link Test...

Страница 6: ...o Feedback potentiometer is required Note Other actuators may have different connections Capacitance probe IN1 IN2 IN3 Connections to EL5600 Series actuators For link position and sensitivity see Prea...

Страница 7: ...12 2 3 1 4 20 mA current loop 1 2 3 4 5 6 7 8 9 10 11 12 4 5 6 1 3 LC2300 Level controller LC2400 Steam meter Level probe Steam Fig 4 Three element level control with pneumatic valve Feedwater LC2300...

Страница 8: ...ttom of the desired proportional band valve fully closed fully open position whichever is most convenient Adjust the LC2200 or LC2300 proportional band potentiometer until the 100 0 amber LED just lig...

Страница 9: ...or a maximum flow of 12 000 kg h The output current of the meter for this size of boiler is Output current 8 000 kg h x 16 4 14 67 mA 12 000 g h Calculate the water calibration value with the followin...

Страница 10: ...amplifier set to high sensitivity range link fitted Riseinwaterlevellessthan140mm PA20preamplifierset to mediumsensitivity rangelink fitted Preamplifier PA20 Medium sensitivity Preamplifier PA20 High...

Страница 11: ...e LC2400 and use figure 6 If the anticipated water level rise is greater than 80 mm and the PA20 is set to high sensitivity or greater than 140 mm and the PA20 is set to medium sensitivity do not inse...

Страница 12: ...nd Safety Executive Guidance Note PM5 For specific instructions for Spirax Sarco systems please see separate literature 9 Fault finding Green LED s not lit No supply from current loop present Loop con...

Отзывы: