![Spirax Sarco LC2300 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/spirax-sarco/lc2300/lc2300_installation-and-maintenance-instructions-manual_1347886004.webp)
IM-P402-72 AB Issue 6
4
Technical data
Maximum ambient temperature
55°C
(131°F)
Minimum ambient temperature
0°C
(32°F)
Pollution degree
2
Overvoltage catagory
I I
Indoor use only
Altitude
2 000 m
(6 561.5 ft)
Humidity
Maximum relative humidity 80% for temperatures up to 31°C (87.8°F)
decreasing linearly to 50% relative humidity at 40°C (104°F).
Protection rating
IP40
Mains supply voltage
230 V setting
198 V - 264 V
115 V setting
99 V - 132 V
Frequency
50 - 60 Hz
Fuse type
20 mm cartridge, 100 mA anti-surge (T). For the UL version, replacement
fuses must be UL recognised to maintain the integrity of the approval.
Maximum power consumption
6 VA
0 - 2 V
Input 1
0 - 6 V
Selectable inputs
0 - 20 mA
4 - 20 mA
Input 2 (opposite sense to input 1)
0 - 20 mA
4 - 20 mA
Note: See separate literature for two element control.
0 - 20mA into 1 k
Ω
maximum
4 - 20mA into 1 k
Ω
maximum
Output (isolated)
or
20 - 0mA into 1 k
Ω
maximum
20 - 4mA into 1 k
Ω
maximum
Wave filter - three stages
Filter 1 position (Minimum damping) 0.07 Hz
Response band width
Filter 2 position (Medium damping)
0.02 Hz
(designed for slowly varying signals)
Filter 3 position (Maximum damping) 0.01 Hz
Set point range
0% - 100% of input
Proportional band range
5% - 100% of input
Transducer supply
24 - 37 Vdc 20 mA maximum
Maximum cable length (controller to probe) 100 m
(328 ft)
Terminal torque rating
1 N m
(9 lbf in)