![Spirax Sarco IBP21 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/spirax-sarco/ibp21/ibp21_installation-and-maintenance-instructions-manual_1347885007.webp)
IM-F01-30
ST Issue 5
7
Limiting conditions
(ISO 6552)
IBP21 and IBP21S
IBP30
ITD32
Steam trap
ITD32
IBP21
IBP21S
IBP30
(psi g)
°C
bar g
(
°F)
(psi g)
°C
bar g
(
°F)
(psi g)
°C
bar g
(
°F)
(psi g)
°C
bar g
(
°F)
Maximum body design
conditions
PN63
PN25
PN25
PN40
PMA -
Maximum allowable
pressure
63
(913)
25
(362)
25
(362)
40
(580)
TMA -
Maximum allowable
temperature
400
(752)
400
(752)
400
(752)
400
(752)
PMO -
Maximum operating
pressure
32
(464)
21
(304)
21
(304)
30
(435)
TMO -
Maximum operating
temperature
240
(464)
240
(464)
240
(464)
240
(464)
Designed for a maximum
cold hydraulic test
pressure of:
95
(1377)
38
(551)
38
(551)
60
(870)
For further details see:
TI-P614-01
TI-P617-01
TI-P617-02
TI-P617-03
IFT14
ISM21
Steam trap
ISM21
IFT14
bar g
°C
(psi g)
(
°F)
bar g
°C
(psi g)
(
°F)
Max. body design conditions
PN25
PN16
PMA - Maximum allowable pressure
25
(362)
16
(232)
TMA - Maximum allowable temperature
400
(752)
250
(482)
PMO - Maximum operating pressure
21
(304)
14
(203)
TMO - Maximum operating temperature
240
(464)
240
(464)
Designed for a maximum cold hydraulic test pressure of:
38
(551)
24
(348)
For further details see:
TI-P618-01
TI-P615-01
Содержание IBP21
Страница 6: ...IM F01 30 ST Issue 5 6 IBP21 and IBP21S ITD32 IBP30 ISM21 IFT14...