Note: Before actioning any maintenance program observe the “General safety

information” in Section 1.

6.1. General Information

Due to the specific set-up of the trap, no special maintenance is required.

The trap operates correctly when the condensation is discharged in blasts, with a time interval

between discharges during which the trap must be perfectly sealed. Inspect and clean the

strainer ensuring that it is not blocked by any deposits or scaling, and replace if needed.

6.2. Replacing internal parts

Warning: before to undertaking any maintenance on the trap it must be isolated from

both the supply line and return line and any pressure allowed to safely normalise to the

atmosphere. The trap should then be allowed to cool.

1.

Open the trap by unscrewing the 6 nuts using a 30 mm spanner.

2.

Dismantle the trim set using the following spanners:
Trim set A

32 mm spanner

Trim set B

36 mm spanner

Trim set C

41 mm spanner

Trim set D

50 mm spanner

3.

After cleaning all joint faces, fit the new unit and tighten with a torque of about 140 N m.

4.

Clean the gasket faces and close the unit, replacing the gasket if it is damaged and tighten in

a crossed sequence.

5.

To replace the strainer, unscrew the screws using a 19 mm spanner; remove the cover and

withdraw the screen and the gasket; fit the new screen and gasket; tighten the two screws

with a torque of about 50 N m.

6. Maintenance

The thermodynamic steam trap discharges condensation with a blast at a very high temperatu-

re; if the trap is to discharge to atmosphere ensure it is piped to a protected and safe place.

5. Operation

4. Commissioning

After installation or maintenance, check that the system works correctly and test all the alarms

and protections devices.

After 24 hours from the start up it is advisable to check the cover nuts tightening acting with a

torque of 100 N m.

Содержание DT300F

Страница 1: ...Thermodynamic Steam Traps Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance 7 Spare parts Th...

Страница 2: ...3 333 5275 247 2...

Страница 3: ...urezza La ghisa un materiale fragile in caso di caduta accidentale il prodotto in ghisa non pi utilizzabile Per informazioni pi dettagliate consultare il manuale d istruzioni del prodotto Rimuovere la...

Страница 4: ...d ariete Prevention of water hammer Scarico condensa nelle linee vapore Steam trapping on steam mains Intervalli di 30 50 m intervals Pendenza Gradient 1 100 Vapore Steam Gruppo di scarico Trap set Co...

Страница 5: ...ducts or re assembling after maintenance Evitare l eccessivo serraggio Utilizzare le coppie di serraggio raccomandate Do not over tighten Use correct torque figures Per garantire l uniformit del caric...

Страница 6: ...rom the bellows manufacturer Guide Guides Distanza breve Short distance Punto di fissaggio Fixing point Movimento assiale Axial movement Distanza media Medium distance Tiranti limitatori Limit rods Pi...

Страница 7: ...Consider flammable materials substances hazardous to health extremes of temperature 1 5 Hazardous environment around the product Consider explosion risk areas lack of oxygen e g tanks pits dangerous g...

Страница 8: ...ing carrying or supporting a load by bodily force can cause injury particularly to the back You are advised to assess the risks taking into account the task the individual the load and the working env...

Страница 9: ...fied at the time of order Available types Four different executions with differentiated internal mechanism type A B C D and sized in accordance to the discharge capacity requirements 2 2 Pipe connecti...

Страница 10: ...imum allowable pressure DT300F A B C 20 C 430 bar g DT300F D 20 C 365 bar g TMA Maximum allowable temperature DT300F A B C 113 bar 560 C DT300F D 100 bar 560 C Minimum allowable temperature 10 C PMO M...

Страница 11: ...3 333 5275 247 7 2 5 Capacities The condensate discharge capacities can be deduced by the diagram below shown Condensate kg h Differential pressure bar g Hot water capacity Cold water capacity...

Страница 12: ...hing that is caused with a very high differential pressure 3 4 With a piped discharge to recovery system the pipe should be sized with a maximum flash steam speed of 20 25 m s 3 5 Do not install the s...

Страница 13: ...trim set using the following spanners Trim set A 32 mm spanner Trim set B 36 mm spanner Trim set C 41 mm spanner Trim set D 50 mm spanner 3 After cleaning all joint faces fit the new unit and tighten...

Страница 14: ...spares Always order spare parts by using the description given in the table and state the type of trap the internal trim set type and size of the connections Example 1 Internal trim set for a DT300F...

Страница 15: ...3 333 5275 247 11...

Страница 16: ...9 17 1 Fax 0362 49 17 307 REPAIRS Please contact our nearest Branch Office or Agent or directrly Spirax Sarco S r l Via per Cinisello 18 20834 Nova Milanese MB Tel 39 0362 49 17 1 Fax 39 0362 49 17 30...

Отзывы: