1. General safety information

Safe operation of these products can only be guaranteed if they are properly installed, commissioned, 

used and maintained by qualified personnel (see Section 1.11) in compliance with the operating 

instructions. General installation and safety instructions for pipeline and plant construction, as well 

as the proper use of tools and safety equipment must also be complied with.

1.1  Intended use

Referring to the Installation and Maintenance Instructions, name-plate and Technical Information 

Sheet, check that the product is suitable for the intended use/application.

The  products  comply  with  the  requirements  of  the  European  Pressure  Equipment  Directive: 

2014/68/EU (PED) falling within category 'SEP'. It should be noted that products within this category 

are required by the Directive not to carry the 

 mark.

Products intended for use in the Naval and Marine sectors are RINA, and M.M.I (Italian navy) approved.

i)   The  products  have  been  specifically  designed  for  use  on  steam,  compressed  air  and  inert 

industrial gases which are in Group 2 of the above mentioned Pressure Equipment Directive. The 

products’ use on other fluids may be possible but, if this is contemplated, Spirax Sarco should 

be contacted to confirm the suitability of the product for the application being considered.

ii)   Check material suitability, pressure and temperature and their maximum and minimum values. 

If the maximum operating limits of the product are lower than those of the system in which 

it is being fitted, or if malfunction of the product could result in a dangerous overpressure or 

overtemperature occurrence, ensure a safety device is included in the system to prevent such 

over-limit situations.

iii)   Determine the correct installation situation and direction of fluid flow.
iv)   Spirax Sarco products are not intended to withstand external stresses that may be induced 

by any system to which they are fitted. It is the responsibility of the installer to consider these 

stresses and take adequate precautions to minimise them.

v)   Remove protection covers from all connections and protective film from all name-plates, where 

appropriate, before installation on steam or other high temperature applications.

1.2 Access

Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting 

to work on the product. Arrange suitable lifting gear if required.

1.3 Lighting

Ensure adequate lighting, particularly where detailed or intricate work is required.

1.4  Hazardous liquids or gases in the pipeline

Consider what is in the pipeline or what may have been in the pipeline at some previous time. 

Consider: flammable materials, substances hazardous to health, extremes of temperature.

Содержание Colima FLU Series

Страница 1: ...I N A B I L I T Y 3 797 5275 200 CH Issue 2 2016 Copyright 2013 Vane Flow Switches Colima FLU Series Installation and Maintenance Instructions 1 General safety information 2 General product informatio...

Страница 2: ...ty of the product for the application being considered ii Check material suitability pressure and temperature and their maximum and minimum values If the maximum operating limits of the product are lo...

Страница 3: ...fore starting work ensure that you have suitable tools and or consumables available Use only genuine Spirax Sarco replacement parts 1 10 Protective clothing Consider whether you and or others in the v...

Страница 4: ...For any safety requirements relating to particular components and or materials used in the product construction please refer to installation and maintenance instructions below 1 16 Disposal This prod...

Страница 5: ...low through heating coil fails 2 1 2 Operating principle Two oscillating magnets on the same axis one integral with the vane and one integral with the elec trical equipment repel each other reciprocal...

Страница 6: ...art Material 1 Housing ALU Rilsan 2 Cover ALU Rilsan 3 Indicator Plexiglass 4 Microswicth Omron Z 15GW4 B 5 Screw AISI 304 6 Magnet Sm Co 7 Flange AISI 304 8 Magnet Sm Co 9 Counter weight AISI 304 10...

Страница 7: ...A Maximum allowable pressure Steel Colima s flange 16 bar g flange sized according to rating 100 bar g 2 4 Models FLU A Gas flow switch with IP 67 aluminum housing Can not be fitted directly on the pi...

Страница 8: ...tighten the instrument and place it in the direction indicated by the arrow on the housing base Caution Always ensure that correct earthing of the equipment is carried out Specific points are set insi...

Страница 9: ...nce 15 mOhm Max Initial value Mechanical life 106 Electrical life 105 V A Load 250 15 0 25 Resistive 15 0 03 Inductive 125 15 0 5 Resistive 15 0 05 Inductive 30 NA 6 Resistive NA 5 Inductive SPDT exec...

Страница 10: ...nstrument does not require preventive maintenance however it is recommended that from time to time a check of the liquid fluidity is actioned to avoid any suspensions or deposits that can influence we...

Страница 11: ...iption given in the column headed Available spares and state the size and serial number of the unit which is indicated on the name plate Example N 1 off Contact for flow switch for Spirax Sarco Colima...