![Spirax Sarco AE36 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/spirax-sarco/ae36/ae36_installation-and-maintenance-instructions-manual_1348000004.webp)
IM-P017-03 ST Issue 5
4
2.3 Pressure /temperature limits
Temperature
°C
Pressure bar g
150
110
100
50
0
0
1
2
3
4
5
6
7
8
9
10
-10
0
100
300
200
20
40
60
80
120
140
100
14
The product should not be used in this region as damage to the internals may occur.
Body design conditions
PN10
PMA Maximum allowable pressure
10 bar g @ 150°C (145 psi g @ 302°F)
TMA
Maximum allowable temperature
150°C
(302°F)
Minimum allowable temperature
-10°C
(14°F)
PMO Maximum operating pressure
10 bar g @ 110°C (145 psi g @ 230°F)
TMO Maximum operating temperature
110°C @ 10 bar g (230°F @ 145 psi g)
Minimum operating temperature
-10°C
(14°F)
D
PMX
Maximum differential pressure
8 bar
(116 psi)
Designed for a maximum cold hydraulic test pressure of:
15 bar g
(217.5 psi g)
Minimum specific gravity of liquid
0.926
Pressure psi g
Temperature
°F